12  
TMC222 DATASHEET (V. 1.12 / March 7, 2011)  
The amount of equivalent full steps during acceleration phase can be computed by the next equation:  
2
2
min  
V
max  
V
N
step  
=
2Acc  
5.1.7 Position Ranges  
Position information is coded by using two’s complement format. Depending on the stepping mode  
(See 5.1.1) the position ranges are as listed in the following table:  
Stepping Mode  
Position Range  
Full range excursion  
Half-stepping  
-4096…+4095  
(-212…+212-1)  
-8192…+8191  
(-213…+213-1)  
-16384…+16383  
(-214…+214-1)  
-32768…+32767  
(-215…+215-1)  
8192 half-steps  
213  
16384 micro-steps  
1/4 micro-stepping  
1/8 micro-stepping  
1/16 micro-stepping  
214  
32768 micro-steps  
215  
65536 micro-steps  
216  
Table 6: Position Ranges  
Target positions can be programmed via serial interface by using the SetPosition command (see  
6.8.11). The actual motor position can be read by the GetFullStatus2 command (see 6.8.2).  
5.1.8 Secure Position  
The GotoSecurePosition command drives the motor to a pre-programmed secure position (see 6.8.4).  
The secure position is programmable by the user. Secure position is coded with 11 bits, therefore the  
resolution is lower than for normal positioning commands, as shown in the following table.  
Stepping Mode  
Half-stepping  
Secure Position Resolution  
4 half steps  
1/4 micro stepping  
1/8 micro stepping  
1/16 micro stepping  
8 micro steps (1/4th)  
16 micro steps (1/8th)  
32 micro steps (1/16th)  
Table 7: Secure Position Resolution  
5.1.9 External Switch SWI  
Pin SWI (see Figure 1, on page 7) will attempt to source and sink current in/from the external switch  
pin. This is to check whether the external switch is open or closed, resp. if the pin is connected to  
ground or Vbat. The status of the switch can be read by using the GetFullStatus1 command. As long  
as the switch is open, the <ESW> flag is set to zero.  
The ESW flag just represents the status of the input switch. The SWI input is intended as a physical  
interface for a mechanical switch that requires a cleaning current for proper operation. The SWI input  
detects if the switch is open or connected either to ground or to Vbat. The SWI input is not a digital  
logic level input. The status of the switch does not automatically perform actions as latching of the  
actual position. Those actions have to be realized by the application software.  
Important Hint: The SWI is not a logic level input as usual; it needs to be connected via 1K resistor  
either to +VBAT or GND;  