欢迎访问ic37.com |
会员登录 免费注册
发布采购

VPL25-1900 参数 Datasheet PDF下载

VPL25-1900图片预览
型号: VPL25-1900
PDF下载: 下载PDF文件 查看货源
内容描述: [Split Bobbin Power Transformer, 25VA, ROHS COMPLIANT]
分类和应用: 变压器
文件页数/大小: 1 页 / 43 K
品牌: TRIAD [ TRIAD MAGNETICS ]
   
P
OWER
T
RANS FOR MER
Chassis Mount : International Series
Electrical Specifications (@25C)
1. Maximum Power: 25.0VA
2. Input Voltage –
Series:
230VAC @ 50/60Hz,
Parallel:
115VAC@ 50/60Hz
1
3. Output Voltage
:
25.2V @ 1.984A
4. Voltage Regulation: 20% TYP @ full load to no load
5. Hipot: 3500VAC between primary to secondary and windings to core.
6. Recommended Fuse
2
:
Littelfuse p/n 313 2.5HXP, 2.5A 250V, slow blow, ¼ x 1 ¼
or,
Cooper Bussmann p/n BK/MDL-2 �½, 2.5A 250V, ¼ x 1 ¼
Dual winding construction with an insulated shroud, both made of a high temperature
material that exceeds UL flammability requirements. Shrouds are provided over the
connections of the leads to the windings on both primary and secondary coils. Devices are
designed with a minimum of 6mm creepage distance between the primary and secondary
and are manufactured with a Class B (130°C) insulation system.
A
BLK
WHT
BRN
BLU
Construction:
E
Agency Files:
UL File: E65390, UL 5085-1 and 3 (formerly UL1585), Class 2/3
cUL: File E65390, For Canadian Use (CSA 22.2, No.66.1-06 and No.66.3-06)
TUV Certificate No.: R72103639, EN60950, Information Technology
YEL
B
RED
Dimensions:
A
2.562
B
4.00
C
2.250
D
3.562
Units: In inches
E
8.00
F
0.187
D
Weight: 2.3 lbs.
Connections
3
:
Input:
Series – BLK to BLU, Jumper WHT to BRN
Parallel – BLK to BLU, Jumper BLK to BRN and WHT to BLU
Output:
RED to YEL
C
F
BLK
RED
RoHS Compliance:
As of manufacturing date February 2005, all standard products meet the
requirements of 2011/65/EU, known as the RoHS initiative.
* Upon printing, this document is considered “uncontrolled”. Please contact Triad Magnetics’
website for the most current version.
1
WHT
BRN
YEL
BLU
Non-Inherently limited. Class 2 not wet, Class 3 wet.
2
Fuse must be used on
secondary
as conditions of acceptability for UL Class2/3 operation.
3
Primary and secondary windings are designed to be connected in series or parallel. Winding are not
intended to be used independently.
SCHEMATIC
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
460 Harley Knox Blvd.
Perris, California 92571
Publish Date: December 4, 2013