Waterflow Detector Specifications  
Engineering Specifications  
Model shall be WFDNFS or WFDNFT as manufactured by System Sensor. Waterflow detectors shall be installed on a 1”, 1¼”., 1½”. or  
2”. CPVC tee manufactured by Tyco, Spears, NIBBCO, or IPEX as designated on the drawing and /or as specified herein. Detectors shall  
mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run at least 6˝ from any fittings or valves  
that may change water direction, flow rate, or pipe diameter or no closer than 24in. from a valve or drain. Detectors shall have a sensitivity  
in the range of 4 to 10 gallons per minute and a static pressure rating of 175 psi. The WFDNFS or WFDNFT detector with incorporated  
time delay mechanism shall respond to waterflow in the specified direction after a preset time delay that is field adjustable. The delay  
mechanism shall be a sealed mechanical pneumatic unit with visual and audible indication of actuation. The actuation mechanism shall  
include a ethylene vinyl acetate vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism.  
Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical  
conduit shall be provided on the detectors. A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by  
Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for indoor or outdoor use.  
Standard Specifications  
Static Pressure Rating  
Maximum Surge  
175 PSI  
Operating Temperature Range 32°F to 150°F (0°C to 60°C)  
18 Feet Per Second (FPS)  
4 – 10 GPM  
Enclosure Rating*  
NEMA 4 – suitable for indoor/outdoor use  
Triggering Threshold  
Bandwidth (Flow Rate)  
Cover Tamper Switch  
Optional, part no. CTS  
Conduit Entrances  
Two openings for ½in. conduit.  
NEMA 4 rated plugs  
Service Use  
Automatic Sprinkler: NFPA-13  
One or Two Family Dwelling: NFPA 13D  
Residential Occupancies up to 4 Stories:  
NFPA 13R  
National Fire Alarm Code: NFPA-72  
Contact Ratings  
Two sets of SPDT (Form C)  
10.0 A, ½ HP @ 125/250 VAC  
2.5 A @ 6/12/24 VDC  
Compatible Tee Fittings 1”  
Warranty  
3 Years  
WFDNFS / WFDNFT Field Wiring Diagram  
Overall Dimensions, Installed WFDNFS,WFDNFT  
3-1/2"  
3-1/2"  
2-5/8"  
2-5/8"  
4-3/32  
4-1/2"  
LOCKING  
COLLAR  
LOCKING  
COLLAR  
TEE  
ADAPTER  
TEE  
ADAPTER  
TEE FITTING  
TEE FITTING  
TEE  
TEE  
DEPTH  
DEPTH  
PLASTIC VANE  
PLASTIC VANE  
W0400-00  
W0401-00  
Ordering Information  
UL Model  
WFDNFS  
WFDNFT  
Description  
Waterflow Detector with Glue In CPVC adapter , Fits 1in., 1¼in., 1½in., 2in. CPVC tees  
Waterflow Detector with Threaded CPVC adapter , Fits 1in., 1¼in., 1½in., 2in. brass threaded and copper sweat tees;  
1in., 1½in. CPVC tees  
Accessories  
FS-RT  
Delay mechanism and switch assembly  
Tamper-proof switch kit  
CTS  
WFDW  
Tamper-proof wrench for cover  
3825 Ohio Avenue • St. Charles, IL 60174  
Phone: 800-SENSOR2 • Fax: 630-377-6495  
www.systemsensor.com  
©2016 System Sensor.  
Product specifications subject to change without notice. Visit systemsensor.com  
for current product information, including the latest version of this data sheet.  
WFDS85300 • 11/16