Architect/Engineer Specifications
The air duct smoke detector shall be a System Sensor
Model DH400ACDCIHT Series Duct Smoke Detector.
The detector shall be UL listed per UL S911, standard
for Smoke Detectors for Duct Applications, specifically
for use in air handling systems. The detector shall oper-
ate at air velocities from 500 feet per minute to 4000
feet per minute. The detector shall have an operating
temperature range of 32˚F to 158˚F. The detector housing
shall be equipped with an integral mounting base capable
of accommodating ionization detector heads. It shall be
capable of local testing via magnetic switch or remote test-
ing using the RTS451KEY or RTS451 Remote Test Station.
The duct detector housing shall incorporate an airtight
smoke chamber in compliance with UL S911. The housing
shall be capable of mounting to rectangular or round ducts
up to 12′ wide without adapter brackets. An integral filter
system shall be included to reduce dust and residue effects
on detector and housing, thereby reducing maintenance
and servicing. Sampling tubes shall be installed after the
housing is mounted to the duct by passing through the duct
housing. Terminal connections shall be of the strip and
clamp method suitable for 14–18 AWG wiring.
Electrical Specifications
PowerꢀSupplyꢀVoltage
20ꢀ-ꢀ29ꢀVDC
24ꢀVACꢀ50ꢀ-ꢀ60ꢀHz
120ꢀVACꢀ50ꢀ-ꢀ60ꢀHz
220/240ꢀVACꢀ50ꢀ-ꢀ60ꢀHz
CURRENTꢀREQUIREMENTSꢀ(USINGꢀNOꢀACCESSORIES)
Max.ꢀstandbyꢀcurrent
Max.ꢀalarmꢀcurrent
25ꢀmA
95ꢀmA
35ꢀmAꢀRMS
55ꢀmAꢀRMS
20ꢀmAꢀRMS
55ꢀmAꢀRMS
20ꢀmAꢀRMS
30ꢀmAꢀRMS
CONTACTꢀRATINGS
Accessory Current Loads at 24 VDC
Alarmꢀinitiationꢀcontactsꢀ(SPST)ꢀꢀ
Alarmꢀauxiliaryꢀcontactsꢀ(DPDT)ꢀꢀ
2.0Aꢀ@ꢀ30ꢀVAC/DCꢀ(0.6ꢀpowerꢀfactor)
Device
Standby
Alarm
10Aꢀ@ꢀ30ꢀVDC
10Aꢀ@ꢀ250ꢀVAC
AP451ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
12mAꢀmax.ꢀ
0mAꢀmax.ꢀꢀ
0mAꢀmax.ꢀꢀ
0mAꢀmax.*ꢀ
12mAꢀmax.*ꢀ
30mAꢀmax.
15mAꢀmax.
7mAꢀmax.
8mAꢀmax.
8mAꢀmax.
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
PA400Wꢀ
RA400Zꢀ
RTS451ꢀ
Troubleꢀcontactsꢀ(SPST)ꢀ
0.3ꢀ@32ꢀVDCꢀ(resistive)
*NOTE:ꢀWhenꢀinitiatingꢀanꢀalarm,ꢀtheꢀRTS451ꢀandꢀRTS451KEYꢀrequireꢀ103mAꢀinꢀalarm.ꢀNominalꢀstandbyꢀ
currentꢀisꢀ0mA.ꢀAlarmꢀcurrentꢀisꢀ8ꢀmAꢀmaximumꢀwhenꢀtestꢀmagnetꢀisꢀremoved.
RTS451KEYꢀ
NOTE:ꢀAccessoriesꢀareꢀonlyꢀratedꢀtoꢀ120°Fꢀandꢀmustꢀbeꢀinstalledꢀindoors.
ANYꢀCOMBINATIONꢀOFꢀACCESSORIESꢀMAYꢀBEꢀUSEDꢀSUCHꢀTHATꢀTHEꢀ
GIVENꢀCURRENTꢀLOADSꢀTOTAL:
ꢀ
ꢀ
100mAꢀORꢀLESSꢀINꢀTHEꢀSTANDBYꢀSTATE,
150mAꢀORꢀLESSꢀINꢀTHEꢀALARMꢀSTATE.
Physical Specifications
Length:
Weight:
AirꢀDuctꢀVelocity:
14.5ꢀinchesꢀ(36.8ꢀcm)
4.5ꢀlbs.ꢀ(2.0ꢀkg)
500ꢀtoꢀ4000ꢀft./min.
Width:
5ꢀinchesꢀ(12.7ꢀcm)
OperatingꢀTemperatureꢀRange:
32ºꢀtoꢀ158ºFꢀ(0ºꢀtoꢀ70ºC)
OperatingꢀHumidityꢀRange:
10%ꢀtoꢀ93%ꢀrelativeꢀhumidity
Depth:
4ꢀinchesꢀ(10.2ꢀcm)
StorageꢀTemperatureꢀRange:
–22ºꢀtoꢀ158ºFꢀ(–30ºꢀtoꢀ70ºC)
Voltage:
24ꢀVAC/VDCꢀorꢀ120/220ꢀVAC
Ordering Information
Modelꢀ
Description
DH400ACDCIHTꢀ 4-wireꢀionizationꢀhigh-temperatureꢀductꢀ
RTS451KEYꢀ
RTS451ꢀ
Remoteꢀtestꢀstationꢀwithꢀkeyꢀ
Remoteꢀtestꢀstationꢀ ꢀ
ꢀ
ꢀ
ꢀ
smokeꢀdetectorꢀ
ꢀ
ꢀ
ꢀ
1451DHHTꢀ
ꢀ
Replacementꢀionizationꢀhigh-temperatureꢀ
sensorꢀhead
PA400Wꢀ
PS24LOWꢀ
RA400Zꢀ
Piezoꢀsounderꢀ(white)
Add-onꢀstrobeꢀ(white)
ST-1.5ꢀ
ST-3ꢀ
Metalꢀsamplingꢀtubeꢀductꢀwidthsꢀ1′–2′
Metalꢀsamplingꢀtubeꢀductꢀwidthsꢀ2′–4′
Metalꢀsamplingꢀtubeꢀductꢀwidthsꢀ4′–8′
Metalꢀsamplingꢀtubeꢀductꢀwidthsꢀ8′–12′
Endꢀcapꢀforꢀmetalꢀsamplingꢀtubes
AnnunciatorꢀwithꢀpiezoꢀalarmꢀandꢀpowerꢀLEDs
WeatherproofꢀOutdoorꢀEnclosureꢀ
RemoteꢀannunciatorꢀalarmꢀLED
Ionꢀcoverꢀremovalꢀtool
CRT400ꢀ
ST-5ꢀ
F36-05-00ꢀ
MOD400Rꢀ
M02-04-00ꢀ
RS14ꢀ
Replacementꢀairꢀfiltersꢀ(twoꢀperꢀpackage)
Sensitivityꢀtestꢀmodule
ST-10ꢀ
P48-21-00ꢀ
APA451ꢀ
DH400OE-1ꢀ
Testꢀmagnet
Ionꢀreplacementꢀscreen
A2650-01ꢀ
Replacementꢀinstallationꢀkitꢀ(mountingꢀhardware)
System Sensor Sales and Service
System Sensor Headquarters
3825ꢀOhioꢀAvenueꢀ
St.ꢀCharles,ꢀILꢀ60174ꢀ
Ph:ꢀ800/SENSOR2ꢀ
Fx:ꢀ630/377-6495ꢀꢀ
www.systemsensor.com
System Sensor Canada
Ph:ꢀ905.812.0767ꢀꢀ
Fx:ꢀ905.812.0771
System Sensor in China
Ph:ꢀ86.29.8832.0119ꢀꢀ
Fx:ꢀ86.29.8832.5110
System Sensor – Far East
Ph:ꢀ85.22.191.9003ꢀꢀ
Fx:ꢀ85.22.736.6580
System Sensor – India
Ph:ꢀ91.124.637.1770ꢀx.2700
Fx:ꢀ91.124.637.3118
System Sensor Europe
Ph:ꢀ44.1403.891920ꢀꢀ
Fx:ꢀ44.1403.891921
System Sensor in Singapore
Ph:ꢀ65.6273.2230ꢀꢀ
Fx:ꢀ65.6273.2610
System Sensor – Australia
Ph:ꢀ613.54.281.142ꢀꢀ
Fx:ꢀ613.54.281.172
System Sensor – Russia
Ph:ꢀ70.95.937.7982
Fx:ꢀ70.95.937.7983