General Description  
All PS12/24ADA Series integrated sounder/strobes are  
suitable for primary signaling in public mode life safety  
intensity, or for 12VDC operation with 15 or 15/75 cd light  
intensity. They feature low current draw with no  
applications. The sounder/strobes can be connected to the measurable in-rush in excess of peak current. The  
alarm indicating circuit of a UL listed fire alarm control  
panel. They are compatible with DC line supervision.  
Panels may have full-wave rectified, unfiltered power  
supplies. The sounder/strobes are available for either  
24VDC operation, with 15, 15/75, 75, or 110 cd light  
sounder/strobe is intended for wall mounting only to a 2″  
electrical backbox. Mounting to a 4square electrical  
backbox can be done with the addition of the PS-FP  
accessory mounting plate.  
Electrical Ratings – Strobe/Mini Horn  
Average Operating  
Average Operating  
Peak  
In-rush Current in  
Current from  
Current from Full Wave  
Model  
Supply  
Voltage Range  
20–30VDC  
20–30VDC  
20–30VDC  
20–30VDC  
10.5–17VDC  
10.5–17VDC  
Operating Current  
Excess of Peak  
Operating Current (mA)  
Regulated Supply  
Rectified, Unfiltered Supply  
Red  
PS2415ADA  
White  
(mA)  
180  
220  
400  
500  
380  
560  
(mA)  
90  
(mArms)*  
105  
PS2415ADAW  
PS241575ADAW  
PS2475ADAW  
PS24110ADAW  
PS1215ADAW  
PS121575ADAW  
0
0
0
0
0
0
PS241575ADA  
PS2475ADA  
PS24110ADA  
PS1215ADA  
PS121575ADA  
108  
185  
225  
185  
240  
135  
215  
260  
212  
285  
* For additional information, see installation manual D900-08-00.  
Actual 12 volt operating voltage cannot be less than 8.5 VDC or greater than 18.7 VDC; actual 24 volt operating voltage cannot be less than 16 VDC or greater than 33 VDC.  
Engineering Specifications  
Sounder/Strobe shall be a System Sensor Model ______  
listed to Standard UL 1971 for the Hearing Impaired and  
shall be approved for Fire Protective Service. Sounder/  
Strobe shall be wired as a Primary Signaling Notification  
appliance. Sounder/strobe shall also comply with the  
Americans with Disabilities Act requirements for visible  
signaling appliances. Sounder/Strobe shall operate on 12  
or 24VDC from a regulated DC supply or full-wave  
rectified, unfiltered supply. The sounder/strobe shall be  
powered from a non-coded power supply. Sounder/Strobe  
shall have no measurable in-rush current in excess of  
operating peak current. Visual signaling devices are to be  
installed in all non-sleeping/corridor and sleeping areas  
per plans and specifications. The strobe light shall consist  
of a xenon flash tube and associated lens/reflector system.  
All sounder/strobes shall be capable of semi-flush wall  
mounting to a standard 2″ × 4″ × 11/  
backbox, without a  
2
separate mounting plate or to a 4″ × 4″ × 11/  
backbox  
2
with a separate mounting plate.  
Standard Light Distribution  
Vertical Dispersion  
Horizontal Dispersion  
Degree  
0
5-30  
35  
Percent of Rating  
ZERO AXIS  
0˚  
0
5
100  
90  
65  
46  
34  
27  
22  
18  
16  
15  
13  
12  
12  
12  
Degree  
0
5-25  
30-45  
50  
55  
60  
65  
70  
Percent of Rating  
100  
90  
75  
55  
45  
40  
35  
35  
30  
30  
25  
25  
40  
–45˚  
45˚  
45  
W
A
L
10  
15  
20  
50  
55  
60  
65  
70  
75  
80  
85  
90  
L
75  
80  
85  
LIGHT  
90  
–90˚  
90˚  
25  
WALL  
90˚ 85 80 75 70 65 60 55 50 45  
FLOOR  
40  
35  
30  
A polar light distribution in both horizontal and vertical directions is mandated for the strobes by the Standard UL 1971 for the Hearing Impaired, with  
specific minimum intensity percentages as shown in the graphs above. With its specially designed lens/reflector system, the PS12/24ADA Strobe  
Retrofit Plate Series meets or exceeds these requirements at all angles.  
Page 2  