Specifications
Size
External/Auxiliary Power Supply Voltage Range
15–30 VDC (filtered)
Air Intake Fan
On 5 seconds every 30 seconds
3.5″ (8.9 cm) H × 6.1″ (15.5 cm) diam,
in B501B-FTX base
External/Auxiliary Power Supply Maximum Current
123 mA
Filter
Weight
Airflow checked every 4 hours
7.3 oz. (207 grams)
External/Auxiliary Power Supply Avg. Current
27 mA
Signaling Line Circuit Supply Range
15–32 VDC
Temperature Range
Detector Current (max. avg.)
32º to 122°F (0° to 50° C)
250 µA @ 24 VDC (without communication)
360 µA @ 24 VDC (one communication every 5
seconds with LED enabled)
Relative Humidity
10% to 93% noncondensing
Filtrex Wiring Diagram
+
–
AUX.
POWER
SUPPLY
+
–
Ordering Information
Model
Description
FTX-P1
Photoelectric smoke detector
FTX-P1A
B501B-FTX
B501B-FTXA
RF-FTX
Photoelectric smoke detector, (Canadian)
Flanged adapter base, 6.1″ (15.5 cm)
Flanged adapter base, 6.1″ (15.5 cm), (Canadian)
Replacement filter cover assembly (6 pack)
Remote LED annunciator, fits U.S. single gang electrical box
Test magnet
RA400Z
M02-04-01
M02-09-00
Test magnet with telescoping handle
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/SENSOR2
Fx: 630/377-6495
Documents-on-Demand
800/736-7672 x3
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor in China
Ph: 86.29.524.6253
Fx: 86.29.524.6259
System Sensor – Far East
Ph: 85.22.191.9003
Fx: 85.22.736.6580
System Sensor – India
Ph: 91.124.637.1770 x.2700
Fx: 91.124.637.3118
System Sensor Europe
Ph: 44.1403.276500
Fx: 44.1403.276501
System Sensor in Singapore
Ph: 65.273.2230
Fx: 65.273.2610
System Sensor – Australia
Ph: 613.54.281.142
Fx: 613.54.281.172
www.systemsensor.com
© 1999 System Sensor. The company reserves the right to change product specifications without notice.
A05-985-01•7/99(10K)•#522