Engineering Specification  
T-Tap style waterflow detector with a solid state retard shall be an Accuflow™ Series model number __________ manufac-  
tured by System Sensor. Waterflow detector shall be installed on a tee that has a 1” NPT branch including: 1”. 1-1/4”, or  
1-1/2” threaded ferrous or brass tee; 1-2” copper sweat tee; 1” CPVC tee; or 1-1/2” polybutylene tee as designated on  
the drawings and/or specified herein. For 2” cast and malleablle threaded tees use 2” paddle (P02-0023-000) provided.  
Detector shall mount on any clear pipe span of the appropriate size, either in a vertical or horizontal run at least 6” from  
any fittings or valves which may change water direction, flow rate, or pipe diameter, or no closer that 24” from a valve or  
drain. For 2” cast and malleablle threaded tees use 2” paddle (P02-0023-000) provided. Detectors shall have a sensitivity  
in the range of 4 to 10 gallons per minute and a static pressure rating of 250 psi. The detector shall respond to water  
flow in the specified direction after a preset time delay. The delay mechanism shall be a solid state unit which is field-  
adjustable via a dipswitch. The actuation mechanism shall include a polyethylene vane inserted through the tee fitting and  
connected by a mechanical linkage to the delay mechanism. Outputs shall consist of one SPDT switch (Form C contact)  
and one SPST switch (normally open) for wiring to an alarm panel or addressable control module and/or bell or notification  
device. Two conduit entrances (one of which is a knockout type) for standard fittings of commonly used electrical conduit  
shall be provided on the detectors. A grounding provision shall be provided. AFDT housing shall be NEMA 4 rated by  
Underwriters Laboratories for indoor/outdoor use. All other models shall be rated for indoor use.  
Standard Specifications  
Static Pressure Rating  
250 PSI  
Current Draw  
300 microamps @ 12/24 VDC or FWR  
400 microamps @ 120 VAC  
Operating Temperature Range  
32°F - 120°F (0°C to 49°C)  
Triggering Threshold Bandwidth (Flow Rate)  
4 - 10 GPM  
Enclosure Rating  
Compatibility  
AFDT:  
UL Indoor/outdoor rated - NEMA 4  
The Accuflow and Accuflow Low Flow detectors  
may receive power and operate on a two-wire initi-  
ating zone of a fire alarm control panel. When  
determining compatibility of these devices, the  
standby operating voltage of the control panel  
must be between 8.5 and 35 volts. In the standby  
mode, each Accuflow and Accuflow Low Flow  
detector acts as a shot across the initiating zone.  
For two wire conventional fire alarm control panels,  
not more than 5 waterflow detectors may be con-  
nected to a single initiating zone. The maximum  
retard/reset time of the waterflow detector plus  
the initiating zone shall not exceed 90 seconds.  
All others: Indoor rated  
Maximum Surge  
18 Feet Per Second (FPS)  
Cover Tamper Switch  
Optional, part no. 546-9000  
Compatible Pipe  
Threaded ferrous and brass tees, copper sweat  
tees, CPVC tees, and polybutylene tees  
Shipping Weight  
2.5 lbs. (1.13 kg)  
Overall Dimensions Installed  
Service Use  
AFDT:  
4.5”H x 3.75”W x 6.7”L  
Automatic Sprinkler: NFPA-13  
One or Two Family Dwelling: NFPA-13D  
Residential Occupancies up to  
4 stories: NFPA-13R  
(11.4cm H x 9.5cm W x 17cm L)  
4.5”H x 3.55”W x 6.7”L  
AFDTH:  
(11.4cm H x 9cm W x 17cm L)  
National Fire Alarm Code: NFPA-72  
Contact Ratings  
For two wire addressable control panels, the num-  
ber of waterflow detectors connected to the  
panel’s signaling line circuit shall be limited by the  
circuit’s current capacity.  
One SPDT (Form C)  
One SPST (normally open)  
0.6 A @ 125 VAC  
2.0 A @ 30 VDC  
Retard Settings  
0 - 90 seconds, in increments of 15 seconds  
Warranty  
3 years  
Conduit Entrances  
Voltage Range  
Two openings for 1/2” conduit, one open, one  
knock-out type  
8.4 - 35 V (DC-FWR)  
108 - 132 VAC  
Ordering Information  
Model Number  
AFDT*  
Description  
Replacement Part Number  
Description  
Waterflow Detector, Fits 1”, 1-1/4”, 1-1/2”  
560-9000  
WFDW  
Cover tamper switch kit  
Tamper proof wrench for cover  
Gasket kit  
ferrous and brass threaded tees; 1”, 1-1/4”,  
1-1/2”, 2” copper sweat tees; 1” CPVC tees;  
and 1-1/2” polybutylene tees  
WFDN4  
PRK9  
Paddle kit - 12 paddles  
Retard PCB kit  
AFDTH*  
Waterflow Detector, Fits 1”, 1-1/4”, 1-1/2”  
ferrous and brass threaded tees; 1”, 1-1/4”,  
1-1/2”, 2” copper sweat tees; 1” CPVC tees;  
and 1-1/2” polybutylene tees  
AFDPCBRK  
.
*ULC version designated with “A” suffix (AFDTA, AFDTHA).  
System Sensor Sales and Service  
System Sensor Headquarters  
3825 Ohio Avenue  
St. Charles, IL 60174  
Ph: 800-SENSOR2  
Fx: 630/377-6495  
Documents On Demand:  
1-800-736-7672 x3  
System Sensor in Canada  
Ph: 905.812.0767  
Fx: 905.812.0771  
System Sensor in China  
Ph: + 86.29.524.6253  
Fx: + 86.29.524.6259  
System Sensor in the Far East  
Ph: + 852.21919003  
Fx: + 852.27366580  
System Sensor in India  
Ph: + 91.11.558.2119  
Fx: + 91.11.567.6815  
System Sensor in Europe  
Ph: + 44.1403.276500  
Fx: + 44.1403.276501  
System Sensor in Singapore  
Ph: + 65.273.2230  
Fx: + 65.273.2610  
System Sensor in Australia  
Ph: + 613.54.281.142  
Fx: + 613.54.281.172  
Web: www.systemsensor.com  
© 2003 System Sensor. The company reserves the right to change product specifications without notice.  
A05-0281-002•1/03(10K)•#1051