Specifications  
Architectural/Engineering Specifications  
Mechanical heat detector shall be a System Sensor 5600 series model number _________, listed to Underwriters Laboratories UL 521 for Heat Detectors for Fire  
Protective Signaling Systems. The detector shall be either a single-circuit or a dual-circuit type, normally open. The detector shall be rated for activation at either  
135°F (57°C) or 194°F (90°C), and shall activate by means of a fixed temperature thermal sensor, or a combination fixed temperature/rate-of-rise thermal sensor.  
The rate-of-rise element shall be activated by a rapid rise in temperature, approximately 15°F (8.3°C) per minute. The detector shall include a reversible mounting  
bracket for mounting to 3½-inch and 4-inch octagonal, single gang, and 4-inch square back boxes with a square to round plaster ring. Wiring connections shall  
be made by means of SEMS screws that shall accommodate 14–22AWG wire. The detector shall contain alphanumeric markings on the exterior of the housing  
to identify its temperature rating and activation method. The rate-of-rise element of combination fixed temperature/rate-of-rise models shall be restorable, to  
allow for field-testing. The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm.  
Physical/Operating Specifications  
Maximum Installation Temperature  
5601P, 5603, 5621, and 5623: 100°F (38°C)  
5602, 5604, 5622, and 5624: 150°F (65.6°C)  
Operating Humidity Range  
5 to 95% RH non-condensing  
Dimensions with mounting bracket  
Diameter: 4.57 inches (11.6cm)  
Height: 1.69 inches (4.3cm)  
Alarm Temperature  
5601P, 5603, 5621, and 5623: 135°F (57°C)  
5602, 5604, 5622, and 5624: 194°F (90°C)  
Weight  
6 oz. (170 grams)  
Rate-of-Rise Threshold  
Mounting  
15°F (8.3°C) rise per minute (models 5601P, 5602, 5621, and 5622 only)  
3½-inch octagonal back box  
4-inch octagonal back box  
Single gang back box  
4-inch square back box with a square to round plaster ring  
Electrical Specifications  
Operating Voltage / Contact Ratings  
6–125VAC / 3A  
6–28VDC / 1A  
125VDC / 0.3A  
250VDC / 0.1A  
Input Terminals  
14–22 AWG  
R
X
X
R
/
/
/
/
5601P  
5602, 5622  
5603, 5623  
5604, 5624  
5621  
Ordering Information  
Identification Method Temperature  
Model  
5601P  
5602  
5603  
5604  
5621  
5622  
5623  
5624  
Circuit  
Single  
Single  
Single  
Single  
Dual  
on Exterior  
Rating  
Activation  
UL Protected Spacing – 10 Foot Ceiling*  
50 feet × 50 feet (15.24m × 15.2m)  
50 feet × 50 feet (15.24m × 15.2m)  
25 feet × 25 feet (7.62m × 7.62m)  
25 feet × 25 feet (7.62m × 7.62m)  
50 feet × 50 feet (15.24m × 15.2m)  
50 feet × 50 feet (15.24m × 15.2m)  
25 feet × 25 feet (7.62m × 7.62m)  
25 feet × 25 feet (7.62m × 7.62m)  
None  
135°F (57°C)  
194°F (90°C)  
135°F (57°C)  
194°F (90°C)  
135°F (57°C)  
194°F (90°C)  
135°F (57°C)  
194°F (90°C)  
Fixed Temperature / Rate-of-Rise  
Fixed Temperature / Rate-of-Rise  
Fixed Temperature  
Lettering  
Lettering  
Lettering  
Lettering  
Lettering  
Lettering  
Lettering  
Fixed Temperature  
Fixed Temperature / Rate-of-Rise  
Fixed Temperature / Rate-of-Rise  
Fixed Temperature  
Dual  
Dual  
Dual  
Fixed Temperature  
*NOTE: Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.  
©2006 System Sensor.  
3825 Ohio Avenue • St. Charles, IL 60174  
Phone: 800-SENSOR2 • Fax: 630-377-6495  
Product specifications subject to change without notice. Visit systemsensor.com for  
current product information, including the latest version of this data sheet.  
A05-0351-002 • 11/06 • #1676