欢迎访问ic37.com |
会员登录 免费注册
发布采购

AQ0500MU12RACFD 参数 Datasheet PDF下载

AQ0500MU12RACFD图片预览
型号: AQ0500MU12RACFD
PDF下载: 下载PDF文件 查看货源
内容描述: 医疗级AC / DC电源,带PFC [Medical Grade AC/DC Power Supply With PFC]
分类和应用: 电源电路医疗功率因数校正
文件页数/大小: 11 页 / 2287 K
品牌: SYNQOR [ SYNQOR WORLDWIDE HEADQUARTERS ]
 浏览型号AQ0500MU12RACFD的Datasheet PDF文件第3页浏览型号AQ0500MU12RACFD的Datasheet PDF文件第4页浏览型号AQ0500MU12RACFD的Datasheet PDF文件第5页浏览型号AQ0500MU12RACFD的Datasheet PDF文件第6页浏览型号AQ0500MU12RACFD的Datasheet PDF文件第7页浏览型号AQ0500MU12RACFD的Datasheet PDF文件第8页浏览型号AQ0500MU12RACFD的Datasheet PDF文件第10页浏览型号AQ0500MU12RACFD的Datasheet PDF文件第11页  
85-264 V  
12/24/36/48V Semi-reg  
500 W Series  
Medical  
AC Input:  
DC Output:  
Power:  
RMS  
.
Grade:  
Technical Specification  
PARALLEL OPERATION - MULTIPLE UNITS  
Chassis configurations for Parallel Units  
Specifications of Parallel Units  
ACuQor units are available either open-frame or pre-mounted As a rule, units wired in parallel behave the same as single units.  
at the factory. Up to 3 units can be mounted into a chassis, in Any specification will remain unchanged that is expressed in units  
either side-by-side or stacked configurations. For a complete list of of voltage, time, frequency, or efficiency. Specifications expressed  
options, see the “Part Numbering System” table on the last page, in terms of power, current, or capacitance, should be scaled by the  
under “Package Type, along with the Mechanical Drawings pages. number of units wired in parallel.  
Only side-by-side configurations can be populated with 500W units,  
since each includes a thermal pad underneath.  
ACuQor units are individually calibrated at the factory, so that the  
output voltage vs. output current characteristic is always consistent  
(see Vout droop characteristic figures). As such, multiple units will  
Interconnection of Parallel Units  
ACuQor units mounted in 2 and 3 unit chassis are not connected share output current accurately. Full current is guaranteed from a  
together. This allows the physical routing and connectivity of the bank of multiple units wired in parallel.  
external wiring to be customized to each application. The following  
table summarizes the recommended wiring to operate multiple  
units in parallel:  
Output Connector Signal  
REMOTE_ENABLE  
FAN_GOOD  
Suggested Connection  
Behavior with Multiple Units  
Wire in parallel  
Inputs activated simultaneously  
Wired-OR outputs – can be pulled low by any unit during an abnormal condition.  
AC_POWER_GOOD  
DC_POWER_GOOD  
VOUT(+), VOUT(-)  
12V_STANDBY*  
5V_STANDBY  
Built-in droop characteristic ensures graceful current sharing.  
Do not wire in parallel Fully regulated characteristic does not support current sharing. If placed in  
parallel, only the output with the highest set-point will drive current.  
*Note: Triple output models only.  
Product # AQ0500MUxx Series  
Phone 1-888-567-9596  
www.synqor.com  
Doc.# 005-005046 Rev. 1  
09/04/08  