85-264 V
12/24/36/48V Semi-reg
400 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
INSTALLATION INSTRUCTIONS
General:ꢀꢀACuQorꢀAC/DCꢀpowerꢀsuppliesꢀareꢀintendedꢀforꢀuseꢀ
asꢀ componentsꢀ inꢀ industrialꢀ equipment.ꢀ ꢀ ACuQorꢀ unitsꢀ mustꢀ beꢀ
properlyꢀinstalledꢀwithinꢀendꢀuseꢀequipmentꢀbeforeꢀtheyꢀcanꢀbeꢀ
safelyꢀappliedꢀasꢀdescribedꢀinꢀthisꢀdocument.ꢀꢀTheꢀsuitabilityꢀofꢀ
theꢀACuQor/equipmentꢀcombinationꢀmustꢀbeꢀverifiedꢀthroughꢀendꢀ
productꢀinvestigation.
Output:ꢀꢀReferꢀtoꢀtheꢀConnectorꢀDetailsꢀsectionꢀforꢀoutputꢀcon-
nectorꢀ wiringꢀ andꢀ signalꢀ I/Oꢀ functionality.ꢀ ꢀ Referꢀ toꢀ nameplateꢀ
labelꢀ forꢀ outputꢀ currentꢀ ratings.ꢀ ꢀ Mainꢀ DCꢀ outputꢀ (Vout+,ꢀ Vout-)ꢀ
pinsꢀshouldꢀuseꢀ20ꢀAWGꢀ(0.5mm2)ꢀwireꢀsize.ꢀꢀIndividualꢀmainꢀ
outputꢀpinsꢀshouldꢀnotꢀbeꢀloadedꢀtoꢀmoreꢀthanꢀ5.5ꢀA.ꢀꢀForꢀcurrentsꢀ
greaterꢀthanꢀ5.5ꢀA,ꢀmultipleꢀmainꢀoutputꢀpins/wiresꢀmustꢀbeꢀusedꢀ
inꢀparallel.ꢀꢀAllꢀsignalꢀI/OꢀpinsꢀareꢀreferencedꢀtoꢀVout-.ꢀ
Mounting:ꢀꢀReferꢀtoꢀtheꢀMechanicalꢀDrawingsꢀsection.ꢀꢀACuQorꢀ
unitsꢀareꢀprovidedꢀwithꢀthreadedꢀstainless-steelꢀstand-offsꢀorꢀinsertsꢀ
forꢀmounting.ꢀꢀThisꢀmountingꢀhardwareꢀisꢀinternallyꢀconnectedꢀtoꢀ
theꢀ inputꢀ connectorꢀ protective-earthꢀ terminalꢀ forꢀ functional-earthꢀ
EMCꢀcontrol.ꢀꢀAnyꢀorientationꢀ(vertical,ꢀhorizontal,ꢀetc.)ꢀmayꢀbeꢀ
used.ꢀꢀAdequateꢀairꢀspaceꢀshouldꢀbeꢀprovidedꢀoverꢀtheꢀfanꢀintakeꢀ
(top)ꢀ andꢀ exhaustꢀ (sides)ꢀ toꢀ allowꢀ forꢀ exchangeꢀ ofꢀ coolingꢀ air.ꢀ
ACuQorꢀisꢀdesignedꢀforꢀaꢀpollutionꢀdegreeꢀ2ꢀenvironment.ꢀꢀTheꢀ
suitabilityꢀofꢀtheꢀenclosedꢀACuQorꢀmechanicalꢀassembliesꢀmustꢀbeꢀ
verifiedꢀthroughꢀendꢀproductꢀinvestigation.
EMC:ꢀꢀACuQorꢀproductsꢀhaveꢀbeenꢀtestedꢀtoꢀtheꢀEMCꢀspecifica-
tionsꢀlistedꢀinꢀtheꢀElectricalꢀCharacteristicsꢀsection.ꢀꢀHowever,ꢀendꢀ
useꢀequipmentꢀmustꢀbeꢀtestedꢀtoꢀverifyꢀEMCꢀcompliance.
Hipot Testing:ꢀ ꢀ ACuQorꢀ productsꢀ areꢀ ratedꢀ forꢀ Hipotꢀ testingꢀ
levelsꢀ ofꢀ1500ꢀVacꢀ inputꢀtoꢀprotective-earth,ꢀ500ꢀVacꢀoutputꢀtoꢀ
protective-earth,ꢀandꢀ3000ꢀVacꢀinputꢀtoꢀoutput.ꢀꢀWhenꢀperform-
ingꢀ theꢀ 3000ꢀ Vacꢀ inputꢀ toꢀ outputꢀ test,ꢀ theꢀ testꢀ voltageꢀ mustꢀ beꢀ
balancedꢀevenlyꢀ1500ꢀVacꢀinputꢀandꢀoutputꢀtoꢀprotective-earth.ꢀ
Twoꢀoppositelyꢀphasedꢀtestꢀvoltageꢀsourcesꢀorꢀaꢀsingleꢀtestꢀvolt-
ageꢀsourceꢀwithꢀexternalꢀbalancingꢀimpedancesꢀ(capacitors)ꢀmayꢀ
beꢀusedꢀtoꢀpreventꢀoverstressingꢀinputꢀorꢀoutputꢀtoꢀprotective-earthꢀ
insulationꢀperꢀIEC/ENCꢀ60950-1.
Encased models:ꢀ ꢀ Aꢀ minimumꢀ ofꢀ 5ꢀ mmꢀ electricalꢀ clearanceꢀ
shouldꢀbeꢀallowedꢀfromꢀtheꢀconnectorꢀendsꢀofꢀencasedꢀmodels.
Input:ꢀꢀReferꢀtoꢀtheꢀConnectorꢀDetailsꢀsectionꢀforꢀinputꢀconnec-
torꢀwiring.ꢀꢀACuQorꢀproductsꢀrequireꢀaꢀsingleꢀphaseꢀACꢀpowerꢀ
sourceꢀofꢀ100-240Vꢀ50/60Hzꢀnominal.ꢀꢀReferꢀtoꢀnameplateꢀlabelꢀ
forꢀ inputꢀ currentꢀ ratings.ꢀ ꢀ Aꢀ protective-earthꢀ connectionꢀ isꢀ alsoꢀ
required.ꢀ ꢀ Minimumꢀ wireꢀ sizeꢀ ofꢀ 18ꢀ AWGꢀ (0.8mm2)ꢀ isꢀ recom-
mended.ꢀꢀBothꢀsidesꢀofꢀtheꢀACꢀlineꢀareꢀinternallyꢀfusedꢀ(seeꢀtableꢀ
forꢀspecificꢀmodels).ꢀꢀTheseꢀfusesꢀareꢀnotꢀuserꢀreplaceable.
MODEL
AQ0300
AQ0400
AQ0500
Input Fuses (in Both AC Lines)
Littelfuseꢀ6.3Aꢀ250Vꢀ21606.3XEP
Littelfuseꢀ6.3Aꢀ250Vꢀ21606.3XEP
Littelfuseꢀ10.0Aꢀ250Vꢀ216010XEP
Fuses Total
2
2
2