85-264 V
12/24/36/48V Semi-reg
300 W Series
Medical
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
CONNECTOR DETAILS
OUTPUT CONNECTOR PINOUT (top side)
Pin 1 FAN_GOOD
Open collector with internal 5V pullup. See Figure A.
Pulsed low on fan failure, 100ms, 50% duty.
Short to VOUT(-) to disable fan.
Pin 2 AC_POWER_GOOD
Pin 3 DC_POWER_GOOD
Open collector with internal 5V pullup. See Figure B.
Pulled low on AC power dropout.
Figure A: Fan status output / Fan enable input interface circuitry.
Open collector with internal 5V pullup. See Figure B.
Pulled low during startup ramp and within 5 ºC of
temperature shutdown threshold.
Pin 4 5V_STANDBY
Pin 5 VOUT(+)
Pin 6 VOUT(+)
Pin 7 VOUT(+)
Pin 8 VOUT(+)
Pin 9 Reserved
Pin 10 Reserved
Pin 11 REMOTE_ENABLE
5 V @ 50 mA available whenever AC power is applied.
Positive Output Voltage.
Positive Output Voltage.
5V_STANDBY
Positive Output Voltage.
Positive Output Voltage.
1N4148
Reserved for future use.
5 k
Reserved for future use.
10 Ohms
AC_POWER_GOOD or
2N3904
Logic input. See Figure C.
Pull high to enable main output.
DC_POWER_GOOD
From AC/DC
0.1 µF
Monitor
Circuitry
Pin 12 VOUT(–)
Pin 13 VOUT(–)
Pin 14 VOUT(–)
Pin 15 VOUT(–)
Pin 16 VOUT(–)
Negative Output Voltage.
Negative Output Voltage.
Negative Output Voltage.
Negative Output Voltage.
Negative Output Voltage.
V
OUT(-)
Figure B: Power good interface circuitry.
12 V OUTPUT CONNECTOR PINOUT (bottom side)
5V_STANDBY
5V_STANDBY
Pin 1 VOUT(+)
Pin 2 VOUT(+)
Pin 3 VOUT(+)
Positive Output Voltage.
Positive Output Voltage.
Positive Output Voltage.
Positive Output Voltage.
Negative Output Voltage.
Negative Output Voltage.
Negative Output Voltage.
Negative Output Voltage
10 Ohms
5 k
To Enable
Circuitry
REMOTE_ENABLE
0.1 µF
10k
VOUT(+)
Pin 4
VOUT(-)
Pin 5 VOUT(–)
Pin 6 VOUT(–)
Pin 7 VOUT(–)
Pin 8 VOUT(–)
Figure C: Remote enable interface circuitry.
MATING CONNECTORS
Connector
Type
Contact
OUTPUT (16 pins)
12V_OUTPUT (8 pins)
INPUT
Molex 430251600
Molex 436450800
JST VHR-5N
Molex 430300008*
Molex 430300008*
JST SVH-41T-P1.1
INDIVIDUAL INPUT CONNECTOR PINOUT
Pin 1
Pin 3
Pin 5
Ground
AC Neutral
AC Line
* Each contact rated for a maximum of 5.5 A.
Product # AQ0300MUxx Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005044 Rev. A
09/09/08
Page 10