Fan Control Device with Hardware Monitoring and Acoustic Noise Reduction Features  
Datasheet  
6.1.4  
Fan Speed Monitoring  
The chip monitors the speed of the fans by utilizing fan tachometer input signals from fans equipped  
with tachometer outputs. The fan tachometer inputs are monitored by using the Fan Tachometer  
registers. These signals, as well as the Fan Tachometer registers, are described below.  
The tachometers will operate in one of two modes:  
Mode 1: Standard tachometer reading mode. This mode is used when the fan is always powered  
when the duty cycle is greater than 00h.  
Mode 2: Enhanced tachometer reading mode. This mode is used when the PWM is pulsing the fan.  
6.1.4.1  
6.1.4.2  
TACH Inputs  
The tachometer inputs are implemented as digital input buffers with logic to filter out small glitches on  
the tach signal.  
Selecting the Mode of Operation:  
The mode is selected through the Mode Select bits located in the Tach Option register. This Mode  
Select bit is defined as follows:  
0=Mode 1: Standard tachometer reading mode  
1=Mode 2 (default): Enhanced tachometer reading mode.  
Default Mode of Operation:  
Mode 2  
Max stretch time (800msec)  
Slow interrupt enabled (Force FFFEh)  
Tach interrupt enabled via enable bit  
Tach Limit = FFFFh  
Look for 5 tach edges  
Don’t ignore first 3 edges after guard time  
Guard Time = 32 clock periods (1 clock period = 1/90kHz).  
Tach readings updated once a second  
6.1.4.3  
Mode 1 – Always Monitoring  
Mode 1 is the simple case. In this mode, the Fan is always powered when it is ‘ON’ and the fan  
tachometer output ALWAYS has a valid output. This mode is typically used if a linear DC Voltage  
control circuit drives the fan. In this mode, the fan tachometer simply counts the number of 90kHz  
pulses between the programmed number of edges (default = 5 edges). The fan tachometer reading  
registers are continuously updated.  
Notes:  
Some enhanced features added to support Mode 2, are available to Mode 1 also. They are:  
programmable number of tach edges and force tach reading register to FFFEh to indicate a SLOW  
fan.  
Five edges or two tach pulses are generated per revolution.  
The counter is used to determine the period of the Fan Tachometer input pulse. The counter starts  
counting on the first edge and continues counting until it detects the last edge or until it reaches FFFFh.  
If the programmed number of edges is detected on or before the counter reaches FFFFh, the reading  
register is updated with that count value. If the counter reaches FFFFh and no edges were detected  
a stalled fan event has occurred and the Tach Reading register will be set to FFFFh. If one or more  
edges are detected, but less than the programmed number of edges, a slow fan event has occurred  
SMSC EMC6D102  