 浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第19页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第20页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第21页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第22页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第24页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第25页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第26页浏览型号EMC2305-1-AP-TR的Datasheet PDF文件第27页  
Multiple RPM-Based PWM Fan Controller for Five Fans  
Datasheet  
100%  
(optional)  
30% through 65%  
Fan Step  
New Target Count  
Algorithm controlled drive  
Prev Target  
Count = FFh  
¼ of Spin Up Time  
Update Time  
Spin Up Time  
Target Count  
Reached  
Check TACH  
Target Count  
Changed  
Figure 4.2 Spin Up Routine  
4.6.1  
Power Up Options  
The EMC2305 allows for one of four fan speed options upon device power up depending on the status  
of the pull-up resistor on the ADDR_SEL pin and the CLK pin. If the ADDR_SEL pin decode enables  
the CLK pin (see Table 3.1), then the value of the pull-up resistor on the CLK pin is used to determine  
the default fan drive setting (see Section 4.5.1).  
If the Fan drive setting is set at a non-zero value (as determined by the CLK pin), then the drive setting  
will be set to the desired setting. The Spin Up Routine will not be activated. This function does not  
disable the Watchdog timer which will continue to function normally. See Section 4.8.  
4.7  
Ramp Rate Control  
The Fan Driver can be configured with automatic ramp rate control. Ramp rate control is accomplished  
by adjusting the drive output settings based on the Maximum Fan Step Register settings and the  
Update Time settings.  
If the RPM-based Fan Speed Control Algorithm is used, then this ramp rate control is automatically  
used. The user programs a maximum step size for the fan drive setting and an update time. The  
update time varies from 100ms to 1.6s while the fan drive maximum step can vary from 1 count to 31  
counts.  
When a new fan drive setting is entered, the delta from the next fan drive setting and the previous fan  
drive setting is determined. If this delta is greater than the Max Step settings, then the fan drive setting  
is incrementally adjusted every 100ms to 1.6s as determined by the Update Time until the target fan  
drive setting is reached. See Figure 4.3.  
SMSC EMC2305  
Revision 1.1 (10-12-09)  
DATA2S3HEET