 浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第16页浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第17页浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第18页浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第19页浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第21页浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第22页浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第23页浏览型号EMC2302-1-AIZL-TR的Datasheet PDF文件第24页  
Dual RPM-Based PWM Fan Controller  
Datasheet  
After the Spin Up Routine has finished, the EMC2302 measures the TACHx signal. If the measured  
TACH Reading Register value is higher than the Valid TACH Count Register setting, the FAN_SPIN  
status bit is set and the Spin Up Routine will automatically attempt to restart the fan.  
Figure 4.2 shows an example of the Spin Up Routine in response to a programmed fan speed change  
based on the first condition above.  
100%  
(optional)  
30% through 65%  
Fan Step  
New Target Count  
Algorithm controlled drive  
Prev Target  
Count = FFh  
¼ of Spin Up Time  
Update Time  
Spin Up Time  
Target Count  
Reached  
Check TACH  
Target Count  
Changed  
Figure 4.2 Spin Up Routine  
4.7  
Ramp Rate Control  
The Fan Driver can be configured with automatic ramp rate control. Ramp rate control is accomplished  
by adjusting the drive output settings based on the Maximum Fan Step Register settings and the  
Update Time settings.  
If the RPM-based Fan Speed Control Algorithm is used, then this ramp rate control is automatically  
used. The user programs a maximum step size for the fan drive setting and an update time. The  
update time varies from 100ms to 1.6s while the fan drive maximum step can vary from 1 count to 31  
counts.  
When a new fan drive setting is entered, the delta from the next fan drive setting and the previous fan  
drive setting is determined. If this delta is greater than the Max Step settings, then the fan drive setting  
is incrementally adjusted every 100ms to 1.6s as determined by the Update Time until the target fan  
drive setting is reached. See Figure 4.3.  