Dual RPM-Based PWM Fan Controller with Hardware Thermal Shutdown
Datasheet
Table 6.40 Spin Time
SPINUP_TIME[1:0]
1
0
TOTAL SPIN UP TIME
0
0
1
1
0
1
0
1
250 ms
500 ms (default)
1 sec
2 sec
6.26
Fan Step Registers
Table 6.41 Fan Step Registers
ADDR
R/W
REGISTER
B7
B6
B5
B4
B3
B2
B1
B0
DEFAULT
Fan 1 Max
Step
47h
87h
R/W
-
-
32
16
8
4
2
1
10h
Fan 2 Max
Step
R/W
-
-
32
16
8
4
2
1
10h
The Fan Step Registers, along with the Update Time, controls the ramp rate of the fan driver response
calculated by the RPM based Fan Speed Control Algorithm. The value of the registers represents the
maximum step size each fan driver will take between update times (see Section 6.22).
When the FSC algorithm is enabled, Ramp Rate control is automatically used. When the FSC is not
active, then Ramp Rate control can be enabled by asserting the EN_RRC bit (see Section 6.23)
APPLICATION NOTE: The UPDATE bits and Fan Step Register settings operate independently of the RPM based
Fan Speed Control Algorithm and will always limit the fan drive setting. That is, if the
programmed fan drive setting (either in determined by the RPM based Fan Speed Control
Algorithm, the Look Up Table, or by manual settings) exceeds the current fan drive setting
by greater than the Fan Step Register setting, the EMC2104 will limit the fan drive change
to the value of the Fan Step Register. It will use the Update Time to determine how often to
update the drive settings.
APPLICATION NOTE: If the Fan Speed Control Algorithm is used, the default settings in the Fan Configuration 2
Register will cause the maximum fan step settings to be ignored.
The Fan Step Registers are software locked.
SMSC EMC2104
Revision 1.74 (05-08-08)
DATA7S1HEET