Dual RPM-Based PWM Fan Controller with Hardware Thermal Shutdown  
Datasheet  
Table 5.2 TRIP_SET Resistor Setting (continued)  
TTRIP (°C)  
LOW RANGE  
TTRIP (°C)  
HIGH RANGE  
TTRIP (°C)  
LOW RANGE  
TTRIP (°C)  
HIGH RANGE  
RSET (1%)  
RSET (1%)  
83  
84  
85  
86  
87  
88  
89  
90  
91  
115  
116  
117  
118  
119  
120  
121  
122  
123  
698  
750  
115  
116  
117  
118  
119  
120  
121  
122  
60  
147  
148  
149  
150  
151  
152  
153  
154  
92  
7870  
9090  
787  
10700  
12700  
15800  
20500  
29400  
49900  
Open  
845  
909  
953  
1020  
1100  
1150  
5.2  
Fan Control Modes of Operation  
The EMC2104 has four modes of operation for each fan driver. Each mode of operation uses the Ramp  
Rate control and Spin Up Routine.  
1. Direct Setting Mode- in this mode of operation, the user directly controls the fan drive setting.  
Updating the Fan Driver Setting Register (see Section 6.20) will instantly update the fan drive.  
Ramp Rate control is optional and enabled via the EN_RRC bits.  
„ This is the default mode. The Direct Setting Mode is enabled by clearing the LUT_LOCK bit  
in the Look Up Table Configuration Register (see Section 6.32) while the TACH / DRIVE bit  
is set to ‘0’.  
„ Whenever the Direct Setting Mode is enabled the current drive will be changed to what was  
last written into the Fan Driver Setting Register.  
2. Fan Speed Control Mode (FSC) - in this mode of operation, the user determines a target  
tachometer count and the drive setting is automatically updated to achieve this target speed. The  
algorithm uses the Spin Up Routine and has user definable ramp rate controls.  
„ This mode is enabled by clearing the LUT_LOCK bit in the Look Up Table (LUT)  
Configuration Register and setting the EN_ALGO bit in the Fan Configuration Register.  
3. Using the Look Up Table with Fan Drive Settings (Direct Setting w/ LUT Mode) - In this mode of  
operation, the user programs the Look Up Table with fan drive settings and corresponding  
temperature thresholds. The fan drive is set based on the measured temperatures and the  
corresponding drive settings. Ramp Rate control is optional and enabled via the EN_RRC bits.  
„ This mode is enabled by programming the Look Up Table then setting the LUT_LOCK bit  
while the TACH / DRIVE bit is set to ‘1’.  
„ The TACH / DRIVE bit in the Look Up Table Configuration Register MUST be set to ‘1’ or  
the fan drive settings will be incorrectly set. Setting this bit to ‘1’ ensures the settings will be  
PWM settings.  
4. Using the Look Up Table with RPM Target Settings (FSC w/ LUT Mode) - In this mode of operation,  
the user programs the Look Up Table with TACH Target values and corresponding temperature  
thresholds. The TACH Target will be set based on the measured temperatures and the  
corresponding target settings. The fan drive settings will be determined automatically based on the  
RPM based Fan Speed Control Algorithm  
„ This mode is enabled by programming the Look Up Table then setting the LUT_LOCK bit  
while the TACH / DRIVE bit is set to ‘0’  
SMSC EMC2104  
Revision 1.74 (05-08-08)  
DATA2S5HEET