Dual RPM-Based PWM Fan Controller with Hardware Thermal Shutdown  
Datasheet  
Appendix B Look Up Table Operation  
The EMC2104 uses a look-up table to apply a user-programmable fan control profile based on  
measured temperature to each fan driver. In this look-up table, each temperature channel is allowed  
to control the fan drive output independently (or jointly) by programming up to eight pairs of  
temperature and drive setting entries.  
The user programs the look-up table based on the desired operation. If the RPM based Fan Speed  
Control Algorithm is to be used (see Section 6.6), then the user must program an RPM target for each  
temperature setting of interest. Alternately, if the RPM based Fan Speed Control Algorithm is not to be  
used, then the user must program a drive setting for each temperature setting of interest.  
If the measured temperature on the External Diode channel meets or exceeds any of the temperature  
thresholds for any of the channels, the fan output will be automatically set to the desired setting  
corresponding to the exceeded temperature. In cases where multiple temperature channel thresholds  
are exceeded, the highest fan drive setting will take precedence.  
When the measured temperature drops to a point below a lower threshold minus the hysteresis value,  
the fan output will be set to the corresponding lower set point.  
The following sections show examples of how the Look Up Table is used and configured. Each Look  
Up Table Example uses the Fan 1 Look Up Table Registers configured as shown in Table B.1.  
Table B.1 Look Up Table Format  
STEP  
TEMP 1  
TEMP 2  
TEMP 3  
TEMP 4  
LUT DRIVE  
LUT Temp 1  
Setting 1 (52h)  
LUT Temp 2  
Setting 1 (53h)  
LUT Temp 3  
Setting 1 (54h)  
LUT Temp 4  
Setting 1 (55h)  
LUT Drive  
Setting 1 (51h)  
1
LUT Temp 1  
Setting 2 (57h)  
LUT Temp 2  
Setting 2 (58h)  
LUT Temp 3  
Setting 2 (59h)  
LUT Temp 4  
Setting 2 (5Ah)  
LUT Drive  
Setting 2 (56h)  
2
3
4
5
6
7
8
LUT Temp 1  
Setting 3 (5Ch)  
LUT Temp 2  
Setting 3 (5Dh)  
LUT Temp 3  
Setting 3 (5Eh)  
LUT Temp 4  
Setting 3 (5Fh)  
LUT Drive  
Setting 3 (5Bh)  
LUT Temp 1  
Setting 4 (61h)  
LUT Temp 2  
Setting 4 (62h)  
LUT Temp 3  
Setting 4 (63h)  
LUT Temp 4  
Setting 4 (64h)  
LUT Drive  
Setting 4 (60h)  
LUT Temp 1  
Setting 5 (66h)  
LUT Temp 2  
Setting 5 (67h)  
LUT Temp 3  
Setting 5 (68h)  
LUT Temp 4  
Setting 5 (69h)  
LUT Drive  
Setting 5 (65h)  
LUT Temp 1  
Setting 6 (6Bh)  
LUT Temp 2  
Setting 6 (6Ch)  
LUT Temp 3  
Setting 6 (6Dh)  
LUT Temp 4  
Setting 6 (6Eh)  
LUT Drive  
Setting 6 (6Ah)  
LUT Temp 1  
Setting 7 (70h)  
LUT Temp 2  
Setting 7 (71h)  
LUT Temp 3  
Setting 7 (72h)  
LUT Temp 4  
Setting 7 (73h)  
LUT Drive  
Setting 7 (6Fh)  
LUT Temp 1  
Setting 8 (75h)  
LUT Temp 2  
Setting 8 (76h)  
LUT Temp 3  
Setting 8 (77h)  
LUT Temp 4  
Setting 8 (78h)  
LUT Drive  
Setting 8 (74h)  
B.1  
Example #1  
This example does not use the RPM based Fan Speed Control Algorithm. Instead, the Look Up Table  
is configured to directly set a fan drive setting based on the temperature of four of its measured inputs.  
The configuration is set as shown in Table B.2.  
Once configured, the Look Up Table is loaded as shown in Table B.3. Table B.3 shows three  
temperature configurations using the settings in Table B.3 and the final fan drive setting that the Look  
Up Table will select.  
SMSC EMC2104  
Revision 1.74 (05-08-08)  
DATA9S1HEET