RPM-Based Fan Controller with HW Thermal Shutdown  
Datasheet  
The Fan Configuration 2 Register controls the tachometer measurement and advanced features of the  
RPM based Fan Speed Control Algorithm.  
Bit 6 - EN_RRC - Enables ramp rate control when the fan driver is operated in the Direct Setting mode  
or the Direct Setting with LUT mode.  
„
„
‘0’ (default) - Ramp rate control is disabled. When the fan driver is operating in Direct Setting mode  
or Direct Setting with LUT mode, the PWM setting will instantly transition to the next programmed  
setting.  
‘1’ - Ramp rate control is enabled. When the fan driver is operating in Direct Setting mode or Direct  
Setting with LUT mode, the PWM setting will follow the ramp rate controls as determined by the  
Fan Step and Update Time settings. The maximum PWM step is capped at the Fan Step setting  
and is updated based on the Update Time as given by Table 6.32.  
Bit 5 - GLITCH_EN - Disables the low pass glitch filter that removes high frequency noise injected on  
the TACH pin.  
„
„
‘0’ - The glitch filter is disabled.  
‘1’ (default) - The glitch filter is enabled.  
Bits 4 - 3 - DER_OPT[1:0] - Control some of the advanced options that affect the derivative portion of  
the RPM based Fan Speed Control Algorithm as shown in Table 6.34. Note that the default derivative  
options disable the ramp rate control maximum step settings. To take advantage of the full ramp rate  
control, limit derivative options to the disabled or basic derivative settings.  
Table 6.34 Derivative Options  
DER_OPT[1:0]  
1
0
OPERATION  
0
0
No derivative terms used  
Basic derivative. The derivative of the error from  
the current drive setting and the target is added  
to the iterative Fan Drive setting (in addition to  
proportional and integral terms)  
0
1
1
1
0
1
Step derivative. The derivative of the error from  
the current drive setting and the target is added  
to the iterative Fan Drive setting and is not  
capped by the maximum Fan Step Register  
setting.  
Both the basic derivative and the step derivative  
are used effectively causing the derivative term to  
have double the effect of the derivative term  
(default).  
Bit 2 - 1 - ERR_RNG[1:0] - Control some of the advanced options that affect the error window. When  
the measured fan speed is within the programmed error window around the target speed, then the fan  
drive setting is not updated. The algorithm will continue to monitor the fan speed and calculate  
necessary drive setting changes based on the error, however these changes are ignored.  
SMSC EMC2103  
Revision 0.85 (01-29-08)  
DATA5S7HEET