欢迎访问ic37.com |
会员登录 免费注册
发布采购

GPMP600-24 参数 Datasheet PDF下载

GPMP600-24图片预览
型号: GPMP600-24
PDF下载: 下载PDF文件 查看货源
内容描述: [AC-DC Regulated Power Supply Module, 700W]
分类和应用: 输出元件
文件页数/大小: 3 页 / 401 K
品牌: SLPOWER [ SL Power Electronics ]
 浏览型号GPMP600-24的Datasheet PDF文件第2页浏览型号GPMP600-24的Datasheet PDF文件第3页  
GPMP SERIES
SINGLE OUTPUT MEDICAL POWER SUPPLY
High Power Supplies 600/700 Watt AC/DC Universal Input Power Supply
SUMMARY
• 90 -264 Vac nominal input range
• Overvoltage and short circuit protection
• Approved to UL, CSA and EN Standards
• Power Good LED
• Low Leakage
The GPMP Series are universal input AC/DC medically ap-
proved power supplies with power factor correction (PFC) and
up to 700 Watts ouput power. The GPMP product in corporates
‘hot-swap’ capabilities and a handle. The series is approved to
EN60601-1 to reduce design-in time and end system compli-
ance costs
g
All specifications are typical at nominal input, full load at 25
O
C unless otherwise stated
SPECIFICATIONS
OUPUT SPECIFICATIONS
Output Power
Total Regulation
Rise time
Transient response
Temperature Coef-
ficient
Overvoltage protection
Short Circuit protection
block wall
At turn-on
Main output 25%
0.1 A/ms
Integral forced air
700 Watts max.
See table
2.0 s max.
3.5% max. dev. 350
ms
recovery
to 1%
+/-0.03%/oC
125% +/-10%
Yes
INPUT SPECIFICATIONS
Input Voltage range
Input frequency
Input surge current
Ground Leakage current
Input current
Input fuse
264 Vac 60 Hz
120 Vac
230 Vac
F1,F2
Universal input
100-240 nom (85 - 264 max)
Vac
47 Hz to 63 Hz
25 A max.
160
mA
8.5 A
4.5 A
10.0 A
EMC INFORMATION
Conducted emissions
Radiated emissions
Line freq. harmonics
Voltage fluctuations
ESD Air
ESD Contact
Radiated immunity
Fast Transients (EFT)
Line surge immunity
Conducted immunity
Power freq. mag. field
Voltage dip immunity
EN55011
EN55011
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Level B
Level A
Class A
Complies (clause 5b)
8 kV contact
6 kV air
3 V/m
2 kV 5 kHz
1 kV diff /2 kV cm
3 Vrms
3 A/m
Unit will ride through without loss of
output at 75% of rated load with AC
power fail warning.
ENVIRONMENTAL SPECIFICATIONS
Thermal Performance
operating ambient
(see ratings chart)
non-operating
0 - 50
o
C
Convection cooled
Maximum Altitude
Relative Humidity
Vibration (operating)
Vibration (non-operating)
Shock
Shock
operating / non-operating
non-condensing
0.003 g
2
/Hz
0.026 g
2
/Hz
half-sine 20 g
pk
half-sine 40 g
pk
-20
o
C -50
o
C
-40 to +85
o
C
600 Watts
10,000 ft. / 40,000
ft. max.
5% - 95% RH
1.5 g
rms
3 axes 10
min/axis
5.0 g
rms
3 axes, 1
hr/axis
10 ms, 3 axes, 6
shocks total
10 ms, 3 axes, 6
shocks total
Page 1 of 3