Commercial
Model
Medical
Model
RoHS
Suffix*
Voltage
Output
Output
Total
Regulation
Output No.
Output
3.3 V
5.1 V
12 V
Adjustment Maximum (A) Maximum (B) OVP Setpoint
Notes
GPFC250-3.3
GPFC250-5
GPFM250-3.3
GPFM250-5
GPFM250-12
GPFM250-15
GPFM250-24
GPFM250-28
GPFM250-48
G
G
G
G
G
G
G
1
1
1
1
1
1
1
5%
5%
5%
5%
5%
5%
5%
36 A
36 A
15 A
12 A
7.5 A
6.5 A
3.8 A
50 A
50 A
6.2 0.6 V
6.2 0.6 V
14 1.1 V
18.5 1.5 V
28 2.5 V
34 2.8 V
55 4.0 V
2%
2%
2%
2%
2%
2%
2%
C
C
C
C
C
C
C
GPFC250-12
GPFC250-15
GPFC250-24
GPFC250-28
GPFC250-48
21 A
15 V
16.7 A
10.5 A
9 A
24 V
28 V
48 V
5.3 A
* Add “G”suffix to part number for RoHS compliant model.
A. Continuous output rating with unrestricted convection cooling.
B. Continuous output rating with 26cfm airflow or “-C”option. Also one minute peak rating for convection cooled.
C. Add “-C”suffix for factory installed cover with fan option.
GPFC250/GPFM250 MECHANICAL SPECIFICATIONS
INPUT:
TB1
ꢀ
ꢀ
ꢀ
ꢀ
6-32,ꢀ3ꢀPINꢀTERMINALꢀBLOCKꢀ0.375”
PINꢀ1)ꢀACꢀLINE
PINꢀ2)ꢀACꢀNEUTRAL
PINꢀ3)ꢀACꢀGROUND
SIGNALS:ꢀJ2
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
AMPꢀP.C.B.ꢀHEADERꢀP/Nꢀ640456-5
MATINGꢀCONNECTORꢀP/N640440-5
PINꢀ1)ꢀDCꢀGOOD
PINꢀ2)ꢀPOWERꢀFAIL
PINꢀ3)ꢀEXTꢀOFF
PINꢀ4)ꢀ+SENSE
PINꢀ5)ꢀ-SENSE
FAN
ꢀ
ꢀ
ꢀ
ꢀ
AMPꢀP.C.B.ꢀHEADERꢀP/Nꢀ640456-2
MATINGꢀCONNECTORꢀP/Nꢀ640440-2
PINꢀ1)ꢀ-
PINꢀ2)ꢀ+
OUTPUT:
TB2
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
6-32,ꢀ4ꢀPINꢀTERMINALꢀBLOCKꢀ0.375
[9.53mm]CTR
ANꢀOPTIONALꢀBUSꢀBARꢀWITHꢀ10-32
SCREWSꢀONꢀHIGH-CURRENTꢀMODELS
ISꢀAVAILABLEꢀBYꢀADDINGꢀ-BꢀTO
MODELꢀNUMBER
PINSꢀ1-2)ꢀ+Vout
PINSꢀ3-4)ꢀRETURN
16AꢀMAXIMUMꢀRECOMMENDED
ꢀ
CURRENTꢀPERꢀCONNECTORꢀPIN.
ꢀ
ꢀ
MAX.ꢀSCREWꢀPROTRUSIONꢀABOVE
CHASSISꢀ=0.120”ꢀ[3.05MM].
OPTIONAL:ꢀCOVER/FANꢀASSEMBLYꢀ#09-250CF
CANꢀBEꢀINCLUDEDꢀBYꢀADDINGꢀ-CꢀTO
MODELꢀNUMBER
WEIGHT:ꢀ2.9ꢀLBS.ꢀ[1.32ꢀkg]ꢀMAX.
TOLERANCES:ꢀ
X.XX=0.030ꢀ[0.76mm]
X.XXX+0.010ꢀ[0.25ꢀmm]
ꢀ
ꢀ
ENVIRONMENTAL SPECIFICATIONS OPERATING
NON-OPERATING
-40 to +85°C
0 to 95% RH
40 gpk
A. Units should be allowed to warm up/operate under non-condensing
conditions before application of power. Derate output current and total
output power by 2.5% per °C above 50°C.
Temperature (A)
Humidity (A)
Shock (B)
0 to 50°
0 to 95% RH
20 gpk
B. Shock testing—half-sinusoidal, 10 3 ms duration, direction, 3
orthogonal axes, total 6 shocks.
Altitude
-500 to 10,000 ft
1.5 g rms’0.003 g2/Hz 5 g rms’0.026 g2/Hz
-500 to 40,000 ft
C. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350 to
2000Hz, 3 orthogonal axes. Tested for 10 min./axis operating and 1
hr./axis non-operating.
Vibration (C)
SL Power Electronics Corp., 6050 King Drive, Bldg. A, Ventura, CA, 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 Email: info@slpower.com Rev. 4/9/07.
Data Sheet © 2006 SL Power Electronics Inc. The information and specifications contained in this data sheet are believed to be correct at time of publication.
However, SL Power accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specifications are subject to change without notice.