欢迎访问ic37.com |
会员登录 免费注册
发布采购

GPFM115-28 参数 Datasheet PDF下载

GPFM115-28图片预览
型号: GPFM115-28
PDF下载: 下载PDF文件 查看货源
内容描述: [AC-DC Regulated Power Supply Module, 115W]
分类和应用: 输出元件
文件页数/大小: 2 页 / 242 K
品牌: SLPOWER [ SL Power Electronics ]
 浏览型号GPFM115-28的Datasheet PDF文件第1页  
Medical  
Model  
RoHS  
Suffix*  
Voltage  
Output  
Output Ad-  
justment  
Output  
Maximum (A)  
Maximum (B)  
Output Peak  
Total  
Regulation  
OVP  
Setpoint  
Ripple/  
Noise  
Notes  
GPFM115-5  
GPFM115-12  
GPFM115-13  
GPFM115-15  
GPFM115-24  
GPFM115-28  
GPFM115-48  
G
G
G
G
G
G
G
5.1 V  
12 V  
13 V  
15 V  
24 V  
28 V  
48 V  
5%  
5%  
5%  
5%  
5%  
5%  
5%  
12 A  
6.7 A  
6.2 A  
5.3 A  
3.3 A  
2.9 A  
1.7 A  
20 A  
9.6 A  
8.8 A  
7.7 A  
4.8 A  
4.1 A  
2.4 A  
25 A  
10.8 A  
9.9 A  
8.7 A  
5.4 A  
4.6 A  
2.7A  
2%  
2%  
2%  
2%  
2%  
2%  
2%  
6.2 0.6 V  
14 1.1 V  
15 1.1 V  
18.5 1.5 V  
28 2.5 V  
34 2.8 V  
55 4.0 V  
1%  
1%  
1%  
1%  
1%  
1%  
1%  
C
C
C
C
C
C
C
Notes:  
* Add “Gsuffix to part number for RoHS compliant model.  
A. Maximum continuous current rating for unrestricted convection cooling.  
B. Maximum continuous current rating with 150 LFM air or cover option.  
C. Add “-Cafter voltage in model number for cover with fan option.  
GPFM115 MECHANICAL SPECIFICATIONS  
JI INPUT: (AMP P.C.B. HEADER P.N 640445-5)  
PIN 1) AC LINE  
PIN 2) = N/C  
PIN 3) = AC NEUTRAL  
PIN 4) = N/C  
PIN 5) = AC GROUND  
SIGNALS: J2  
AMP P.C.B. HEADER P/N 640456-4  
MATING CONNECTOR P/N 640621-4  
PIN 1) POWER FAIL  
PIN 2) -SENSE  
PIN 3) +SENSE  
PIN 4) COMMON  
FAN: J4  
AMP P.C.B. HEADER P/N 640456-2  
MATING CONNECTOR P/N 640621-2  
PIN 1) -  
PIN 2) +  
OUTPUT  
J3- 5A MAXIMUM CONTINUOUS CURRENT PER  
CONNECTOR PIN.  
AMP P.C.B. HEADER P/N 640445-8  
PIN 1-4) +Vout  
PINS 5-8) RETURN  
OUTPUT-MATING CONNECTOR AMP P/N  
HOUSING 640250-8  
CONTACT 770476-1  
INPUT MATING CONNECTOR AMP P/N  
HOUSING 640250-5  
CONTACT 770476-1  
MAX. SCREW PROTRUSION THROUGH CHASSIS = 0.08”  
[2 MM], CHASSIS THICKNESS = 0.080” [2 MM]  
OPTIONAL COVER/FAN ASSEMBLY  
AVAILABLE P/N 09-115CF  
A. Units should be allowed to warm up/operate under non-condensing  
conditions before application of power. Derate output current and total  
output power by 2.5% per °C above 50°C. For operation in a confined  
space, moving air may be required. Under all conditions, the cooling vs.  
load profile should be such that chassis temperatures do not exceed  
90°C for extended periods.  
ENVIRONMENTAL SPECIFICATIONS OPERATING  
NON-OPERATING  
Temperature (A)  
Humidity (A)  
Shock (B)  
0 to 50°  
-40 to +85°C  
0 to 95% RH  
40 gpk  
0 to 95% RH  
20 gpk  
B. Shock testing—half-sinusoidal, 10 3 ms duration, direction, 3  
orthogonal axes, total 6 shocks.  
Altitude  
-500 to 10,000 ft  
-500 to 40,000 ft  
C. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350 to  
2000Hz, 3 orthogonal axes. Tested for 10 min./axis operating and 1  
hr./axis non-operating.  
Vibration (C)  
1.5 g rms0.003 g2/Hz 5 g rms0.026 g2/Hz  
SL Power Electronics, Inc. 6050 King Drive, Bldg. A, Ventura, CA, 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 Email: info@slpower.com www.slpower.com Rev.  
5/6/08. Data Sheet © 2008 SL Power Electronics, Inc. The information and specifications contained in this data sheet are believed to be correct at time of publication.  
However, SL Power accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specifications are subject to change without notice.