欢迎访问ic37.com |
会员登录 免费注册
发布采购

GLC65-5 参数 Datasheet PDF下载

GLC65-5图片预览
型号: GLC65-5
PDF下载: 下载PDF文件 查看货源
内容描述: [Power Supply Module,]
分类和应用: 输出元件
文件页数/大小: 2 页 / 38 K
品牌: SLPOWER [ SL Power Electronics ]
 浏览型号GLC65-5的Datasheet PDF文件第2页  
GLC65 GLOBAL LOW-COST SWITCHERS
FEATURES:
• Patent Pending
• 4.1W/in
3
• Compact (3.0" x 5.0" x 1.06")
• Ultra-high efficiency (up to 94%)
• Meets harmonic requirements of IEC1000-3-2, Class A
• EMI compliance to CISPR22 Class B
• Approved to UL2601, EN60601, CSA22.2 No. 601.1
• 2-year warranty
marked to LVD
GLOBAL LOW-COST SWITCHERS
SPECIFICATIONS:
AC Input
90-264Vac, 47-63Hz single phase.
Input Current
Meets input current harmonic requirements of IEC1000-3-2. Maximum
input current at minimum output voltage and output overload will be less
than 1.7A.
Output Power
Normal continuous output power is 65W, 75W peak for 60 sec. The
3.3Vdc unit is 36.3W and the 5Vdc unit is 55W continuous.
Hold-Up Time
20mSec from loss of AC input at 65W load, from 120Vac input.
Overload Protection
Fully protected against short circuit and output overload. Short circuit
protection is cycling type power limit on outputs 1 & 2; foldback type on
output 3.
Output Noise
0.5%RMS, 1% pk-pk, 20MHz bandwidth, differential mode. Measured
with scope probe directly across output terminals of the power supply
with load terminated with 0.1µF capacitor.
Transient Response
Main output: 500µSec typical response time for return to within 0.5% of
final value for a 50% load step within the regulation limits of minimum and
maximum load,
∆i/∆t<0.2A/µSec.
Maximum voltage deviation is 3.5%.
Startup/shutdown overshoot less than 3%.
Voltage Adjustment
Adjustable potentiometer capable of
±5%
change from nominal setting.
Overload Protection
Factory set to begin power limiting at approximately 80W.
Efficiency
88 to 94% minimum at full rated load, nominal input voltage, depending
on model.
Leakage Current
Under normal conditions, leakage current is 425µA with 132Vac @ 60Hz
input.
Environmental
Designed for 0 to 50°C operation at full rated output power; derate
output current and total output power by 2.5% per
°C
above 50°C. See
Environmental and Packaging Specifications (p. 11) for additional
information.
Inrush Current
Inrush is limited by internal thermistor. The inrush at 240Vac, averaged
over the first AC half-cycle under cold start conditions will not exceed
37A.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the following emissions
requirements:
EMI SPECIFICATIONS
COMPLIANCE LEVEL
Conducted Emissions
EN55022 Class B; FCC Class B
Static Discharge
EN61000-4-2, 6 kV contact, 8 kV air
RF Field Susceptibility
EN61000-4-3, 3 V/meter
Fast Transients/Bursts
EN61000-4-4, 2 kV, 5 kHz
Surge Susceptibility
EN61000-4-5, 1 kV diff., 2 kV com.
Safety
All GLC models are approved to UL1950, CSA22.2 No. 234 Level 3,
IEC950 and EN60950. Consult factory for approval status.
Condor D.C. Power Supplies, Inc./A subsidiary of SL Industries, Inc.
2311 Statham Parkway, Oxnard, CA 93033 • 800-235-5929 • 805-486-4565 • FAX 805-487-8911 • www.condorpower.com/
44