GEM600
600W Single Output Economy/Technology Switchers
Commercial and Medical 2 Year Warranty
Output Parameters
Volts (V) ┌────── Output Current ───────┐ Ripple
Model
Number
Total
Regulation
OVP
Threshold
Nominal
Peak
27.0A
23.5A
18.0A
13.5A
& Noise
240mV
280mV
360mV
480mV
GEM600-24G
GEM600-28G
GEM600-36G
GEM600-48G
24V
28V
36V
48V
25.0A
1.0%
1.0%
1.0%
1.0%
30.0 2V
33.0 3V
43.0 3V
56.0 4V
21.5A
16.7A
12.5A
Environmental Specifications
Operating Temperature
-20° to 70°C. Derate output power for operation above 50°C. Fan
Temperature Coefficient
0.03% per °C typical on all units.
integral to the power supply.
Storage Temperature
-40 to +85°C
Output Power Derating
Derate Output Power by 2.5% per °C up to 70°C maximum.
Relative Humidity
5% to 95%, non-condensing
Thermal Shutdown
Provided to avoid prolonged over-temperature condition.
Vibration
Operating:
Non-Operating:
Operating Altitude
-500 to 10,000 ft.
0.003 g2/Hz, 1.5 grms overall, 3 axes, 10 min. / axis
0.026 g2/Hz, 5.0 grms overall, 3 axes, 1 hr. / axis
Shock
Operating:
Non-operating Altitude
-500 to 40,000 ft.
Half-sine, 20 gpk, 10 ms, 3 axes, 6 shocks total
Non-Operating: Half-sine, 40 gpk, 10 ms, 3 axes, 6 shocks total
EMI/EMC Compliance
RF Emissions
EN55011/22 and FCC Part 15, radiated Class A, conducted Class B.
EN61000-4-2, 6kV Contact Discharge, 8kV air discharge
EN61000-4-3, 3V/m.
Static Discharge Immunity
Radiated RF Immunity
EFT/Burst Immunity
EN61000-4-4, 2kV/5kHz..
Line Surge Immunity
EN61000-4-5, 1kV differential, 2kV common-mode
EN61000-4-6, 3V
Conducted RF Immunity
Power Frequency Magnetic Field Immunity
Voltage Dip Immunity
EN61000-4-8, 3A/m
EN61000-4-11, see EN60601-1-2: 2001 chart below.
EN61000-3-2, Class A
Line Frequency Harmonics
Voltage Fluctuations/Flicker
EN61000-3-3, Complies (clause 5b)
EN60601-1-2: 2001 Voltage Sag Compliance
Voltage Test Level
Input Voltage
Voltage Dip
Input Voltage
Duration
Periods
Output Voltage
Deviation
100VAC
100VAC
100VAC
240VAC
240VAC
240VAC
<5 VAC
40 VAC
70 VAC
<12 VAC
96 VAC
168 VAC
10mS
100mS
500mS
10mS
<3.5%
<3.5%
<3.5%
<3.5%
<3.5%
<3.5%
100mS
500mS
Note:
During 100mS voltage dip (5 cycles at 40%VAC), the AC Power Fail warning may trigger. During low line 100mS voltage dip, reduced loading to 50%
rated load is required to meet the deviation requirement and regulation.