5 0 0 WATTS
9 .6 5 ” x 5 ” x 2 .1 0 ”
DMX-5 0 0
DMX-500
DMX-500 with Option F
3.7 lbs - 1.7 kgs
3.9 lbs - 1.8 kgs
Dimensions:
Inches
Millimeters
SPECIFICATIONS: ALL MODELS
INPUT
DC Input: 40-60 Vdc range. Internally fused for 25 A.
Efficiency: 75% typical.
OUTPUT
Adjustability: Outputs #1 and 2 user adjustable ±5% minimum. Output #3 tracks #2; initial
accuracy ±4%. Output #4 user adjustable ±5% minimum.
DC INPUT
FUNCTION
TB1- (–)
Line & Load Reg: Outputs #1, 2, and 4 hold ±1% over DC input range and 0 to 100% load
change. Output #3 requires 20% minimum load on outputs #2 and 3 to hold ±4%.
Ripple & Noise: Less than 1% p-p or 100 mV, whichever is greater.
Remote Sense (Outputs #1 and 2): Compensates for 250 mV total line drop. Open sense lead
protection. (See Redundancy, below.)
48 Vdc
CONNECTOR
Barrier strip
-48 VDC Input
#6-32 screws
3/8” centers
TB1- (+)
-48 VDC Return
Safety Ground
Temperature Coefficient (Outputs #1, 2, and 4): 0.02% per degree C.
Stability: 0.1% over 8 hours after 30 minutes warm-up.
TB1-
(
)
Transient Response (Outputs #1, 2, and 4): Output voltage returns to within 1% in less than
500 µs for a 50% load change. Peak transient does not exceed 5%.
Overload Protection: All outputs are protected against overload and short circuit. Automatic
recovery upon removal of fault.
Overvoltage Protection (Outputs #1 and 2): Protects load against power supply induced over-
voltage. Trip point is factory set so that output voltage cannot exceed 136% of nominal.
Peak Output Current: Dual current ratings define continuous and peak currents. The peak cur-
rent shown can be delivered for a maximum period of 30 seconds.
Remote Inhibit: Contact closure to the negative sense line or a TTL level “0” turns off DC
outputs.
Redundancy: External OR-ing diodes and forced current sharing on output #1 provide “N+1”
capability. Remote sense (+S) compensates for additional 0.6 V diode voltage drop.
When the current sharing terminal is connected among units, current sharing remains
within 10% of the unit’s full output current rating.
DC Power Good: Provides a TTL “1” open collector when output #1 is above 4.6 V nominal.
Reverse Voltage: Protected against reverse voltage up to supply current rating.
DC OUTPUT
FUNCTION
LOCATION
NOTES
CONNECTOR
Output #1
Terminal marked +V Main Output
Bus bars
#8-32 screws
Terminal marked -V
J1-5, 10
Rtn (Common)
Rtn (Common)
Rtn (Common)
Output #2
Output #3
Output #4
J1-4, 9
J1-3, 8
AMP #770743-1
mates with connector
#770580-1 with
J1-4, 9
J1-2, 7
(+) Floating
Output
sockets #171639-1
J1-1, 6
(–) Floating
Output
STATUS AND CONTROL
ENVIRONMENTAL
FUNCTION
LOCATION
NOTES
CONNECTOR
Thermal Protection: Shuts down power supply if overheated. Automatic recovery.
Temperature Range: 0° to 50°C at full ratings.
Safety Agencies: Most models are approved to UL1950; CSA 22.2 #234; IEC 950 and TÜV
EN60950, Class 1 SELV., CE 72/23/EEC/93/68EEC (low voltage directive).
Conducted RFI: Meets FCC Part 15, Subpart J, Class A; EN55022 Class B; CISPR 22 Class B.
Cooling: 30 CFM required to achieve full ratings.
Remote Sense
J2-2
J2-1
J2-8
J2-7
J2-3
J2-5
Output #1 Sense
Output #1 Sense Rtn
Output #2 Sense
AMP MTA type
#640456-8 pin
header (locking)
Output #2 Sense Rtn
Reference to Common
DC Power Good
Inhibit
Output Isolation: Isolated from ground 50 Vdc.
Reference to Common
when #1 Sense Rtn
is terminated.
OPTIONS:
Option “F”, Fan/Cover Assembly: Cover with integral ball-bearing fan provides proper cool-
ing to achieve full ratings at 50°C ambient temperature. 2.10” dimension increases to 3.31”. Current Share
J2-6
J3-1
J3-2
Option “V”, Fan/Cover Assembly: Low profile, end venting cover with integral ball-bearing fan.
Aux. Fan Voltage
(Not available with
“V” or “F” options)
+12V @ 0.5A Output
Rtn (Common)
AMP MTA type
#640456-2 pin
header (locking)
2.10” dimension increases to 2.50”, and 9.65” dimension increases to 11”.
Consult factory for other available options.
Condor D.C. Power Supplies, Inc., A subsidiary of SL Industries, Inc. 805-486-4565 • (800) 235-5929 Fax: (805) 487-8911 http://www.condorpower.com