Installation
8.1
MechanicalInstallation
Installation location and conditions
The operating unit is designed for installation in the front panels of cabinets and
consoles. Cut a mounting cut-out in the front panel in preparation for installation of
the unit. The thickness of the front panel must not exceed 6 mm. No other holes
need to be drilled for mounting.
Details regarding the mounting depth and mounting cut-out are provided on
page 9-2.
Degree of protection
The IP65 degree of protection for the front panel can only be ensured when the
seal on the front plate of the operating unit is fitted correctly.
Caution
!
S The unit must be brought to room temperature before it is commissioned. If
condensation forms, do not switch the unit on until it absolutely dry.
S To prevent the operating unit overheating during operation,
– the angle of inclination from vertical installation may not exceed a maximum
of $35_.
– do not expose the operating unit to direct sunlight
– ensure that the ventilation slits in the housing remain free after installation.
S When the cabinet is opened, certain parts of the system that may conduct
hazardous voltage are exposed.
S The unit was function-tested before shipping. If a fault occurs nevertheless,
please enclose a full account of the fault when returning the unit.
TP070 Equipment Manual
Release03/00
8-2