3RT, 3TB, 3TF Contactors for Switching Motors  
3RT10 contactors, 3-pole, 3 ... 250 kW  
Control circuit:  
$ Solid-state module of  
L1/L+  
N/L-  
3RT1 ...-.Q contactor  
• Contactor control through AS-Interface by way of terminals  
AS-i +/AS-i –. Each of these terminals is jumpered and  
connected twice to a 4-pole connector which is separate from  
the other control inputs.  
2
A1 A2  
% Plug-in connection, 6-pole  
& Plug-in connection, 4-pole  
S2  
H1  
H2  
H3  
S1  
Advantages:  
S1 Selector switch for switching  
from automatic control,  
e.g. by means of AS-Interface,  
to local control  
e.g.  
Overload relay  
3RB20  
SF1  
SF2  
AS-i  
AS-i  
AS-i  
AS-i  
- The AS-Interface cable is not interrupted if the connector is  
pulled out  
AS-i  
- The contactor remains functional through the local control  
inputs and its own 6-pole connector  
S1 open: Automatic mode  
• Control signals through AS-i:  
- Contactor ON/OFF  
NSB0_01149b  
S2 Local control option  
1
3
• Status signals through AS-i:  
- Contactor ON/OFF  
Possibility of switching from automatic control to local control by  
means of terminals H1/H2/H3, i.e. automatic control through  
AS-Interface can be deactivated e.g. during startup or in the  
event of a fault and the contactor can be controlled manually.  
- Automatic/Local control:  
- Remaining lifetime (RLT)  
- Signal through free input, e.g. overload relay tripped.  
I/O configuration (hex)  
ID code (hex)  
7
F
Power supply  
V
26.5 ... 31.6 (according to AS-Interface specification)  
AS-Interface current input  
Contact loading at SF1/2  
mA  
mA  
max. 20  
3 ... 6  
Watchdog function (disconnects outputs in the event of AS-Interface fault)  
Built-in  
LED  
States  
On  
Description of state  
Indication behavior  
AS-Interface  
On  
Flashing Flashing  
During operation, the LEDs on  
the contactor indicate the  
states shown on the right.  
Station address 0  
No AS-Interface communication  
AS-Interface communication OK  
Contactor diagnostics using the application program  
• Inputs  
Outputs  
Input signals  
Device status  
Output signals  
Device status  
DI0  
"Ready"  
0
1
0
1
0
1
0
1
Device not ready/manual operation  
Device ready/automatic operation  
Contactor off  
DO0  
DO1  
DO2  
DO3  
"Running"  
0
1
0
1
0
1
0
1
Contactor off  
Contactor on  
DI1  
DI2  
DI3  
"Running"  
--  
--  
--  
--  
--  
--  
Contactor on  
"Remaining lifetime"  
"Free input"  
Remaining lifetime RLT > 20 %  
Remaining lifetime RLT ˆ 20 %  
No input signal at SF1/2  
Input signal at SF1/2  
Siemens LV 1 · 2006  