Surge Tolerant Fuses  
2. UL1459/1950  
3. GR 1089  
Test circuit  
Test circuit  
t = 1,5 s/5 s/ 30 Min.  
R
I
267 µH  
D
puls  
R
D
68 Ω  
+
20 µF  
Fuse  
Fuse  
50 kΩ  
R
M
I
= 40 A/7 A/2.2. A  
sc  
Fig. 4  
Test 1:  
Pulse current  
Generator no load  
The fuse in the test current circuit is loaded with a test current  
of ISC = 40 A .  
The AC 600 V / 50 Hz source voltage is applied for a total  
of 1.5 sec.  
50%  
t1=10µs  
Requirement: The fuse shall interrupt the circuit.  
t2=1000µs  
Test 2:  
The fuse in the test current circuit is loaded with a test current  
of ISC = 7 A .  
Fig. 5  
The AC 600 V / 50 Hz source voltage is applied for a total  
of 5 sec.  
Test:  
1. The pulse amplitude (generator no-load) is set to 1000 V  
and the pulse shape to 10 µs / 1000 µs.  
Requirement: The fuse shall interrupt the circuit.  
Test 3  
2. The pulse current Ipuls is set to the value Ipuls max. stated in  
the data sheet with limiting resistor RD.  
The fuse in the test current circuit is loaded with a test current  
of ISC = 2,2 A .  
3. Test mode: 50 single pulses, at an interval of 60 sec.  
alternating polarity.  
The AC 600 V / 50Hz source voltage is applied for at least  
30 minutes, or until stable thermal conditions are achieved  
in the telecom unit or until the fuse interrupts the circuit.  
This test is performed together with the equipment in which the  
fuse is installed.  
Requirement: The fuse shall not interrupt the circuit.  
5) Note: With a charge voltage of UC = 1000 V, the standar-  
dized pulse generator in Fig. 5 supplies a maximum pulse  
current Ipuls = 14 A, providing the current limiting resistor is  
RD = 0. The shunt RM for the current monitoring has a very  
low resistance and has no notable influence to the current  
amplitude. This means that the data sheet current 14 A (5) does  
not represent the maximum permissible pulse amplitude of the  
fuse in question, but the maximum current amplitude which can  
be supplied by the pulse generator. If a max. current higher  
than 14 A is to be expected in a circuit, the  
I2t- values of the fuse can be calculated using the formula I2t =  
0,72 x i2peak x t2, as a good approximation in order that the  
selected fuse can accept the expected current pulse without  
interrupting the circuit.  
Schurter, Inc. • Phone 707-778-6311 • Fax 707-778-6401 • E-mail: info@schurterinc.com • Website http://www.schurterinc.com  