Product datasheet
Characteristics
A9D01806
Acti9 iC60H RCBO plug on neutral - 1P+Ns - 6A -
C - 10000A - 10mA - type A
Main
Circuit breaker application
Range
Product name
Product or component type
Device short name
Poles description
[In] rated current
Earthing system
Curve code
Earth-leakage sensitivity
Breaking capacity
Distribution
Acti9
Acti9 iC60 RCBO
Residual current breaker with overcurrent protection (RCBO)
IC60H RCBO PoN
1P + Ns
6 A at 50 °C
TN
C
10 mA
10000 A Icn at 240 V AC 50/60 Hz conforming to IEC 61009-2-2
Complementary
Neutral position
Number of protected poles
Device location in system
Network type
Network frequency
[Ue] rated operational voltage
Trip unit technology
Magnetic tripping limit
Residual current tripping technology
Earth-leakage protection time delay
Earth-leakage protection class
[Ics] rated service breaking capacity
Electrical insulation class
Limitation class
Aug 15, 2019
Left
1
Outgoer
AC
50/60 Hz
230/240 V AC 50/60 Hz
Thermal-magnetic
5...10 x In
Voltage dependent
Instantaneous
Type A
7500 A at 240 V AC 50/60 Hz conforming to IEC 61009-2-2
Class II
3
1