Specifications
Magnecraft
™
General Purpose Relays
788 Series
SPDT, DPDT, 3PDT 12 A
Specifications (UL 508)
Part Number
Contact Characteristics
Terminal Style
Contact Configuration
Maximum Current
Current Rating with Magnetic Blowout (69 feature)
Contact Materials
Maximum Switching Voltage
Rated Switching Current at Voltage
Blade
SPDT
12 A
–
Silver Alloy
300 V
Resistive:
12 A at 120 Vac 50/60 Hz; 16 A at 277
Vac 50/60 Hz; 16 A at 28 Vdc
Motor:
1/2 hp at 240 Vac 50/60 Hz;1/3 hp at 120
Vac 50/60 Hz
Pilot Duty:
B300
–
100 mA at 5 Vdc (0 .5 W)
Blade
DPDT/3PDT
12 A
3 A at 150 Vdc (DPDT only)
Silver Alloy
300 V
Resistive:
12 A at 120 Vac 50/60 Hz; 16 A at 277
Vac 50/60 Hz; 16 A at 28 Vdc
Motor:
1/2 hp at 240 Vac 50/60 Hz; 1/3 hp at 120
Vac 50/60 Hz
Pilot Duty:
B300
3 A at 150 Vdc
100 mA at 5 Vdc (0 .5 W)
788XAX
788XBX/XCX
Rated Current with Magnetic Blowout (Code 69)
Minimum Switching Requirement
Coil Characteristics
Maximum Operating Voltage
Maximum Pickup Voltage
Drop-out Voltage Threshold
Average Consumption
General Characteristics
Electrical Life at Rated Load
Mechanical Life (Unpowered)
Operating Time (Response Time)
Dielectric Strength - Between Coil and Contact (AC)
Dielectric Strength - Between Poles (AC)
Ambient Air Temperature around the Device -
Storage
Ambient Air Temperature around the Device -
Operation
Vibration Resistance - Operational
Shock Resistance
Degree of Protection
Weight
Agency Approvals
110% (AC / DC)
85% (AC); 80% (DC)
15% (AC); 10% (DC)
3 VA (AC); 1 .4 W (DC)
110% (AC / DC)
85% (AC); 80% (DC)
15% (AC); 10% (DC)
3 VA (AC); 1 .4 W (DC)
100,000 operations
5,000,000 operations
20 ms
2500 V(rms)
2500 V(rms)
-40 – +85 °C (-40 – +185 °F)
-40 – +55 °C (-40 – +131 °F)
3 g-n at 10-55 Hz
10 g-n
IP 40
88 g (3 .10 oz)
UL with socket, UR (E43641), CE, CSA (LR40787),
RoHS
100,000 operations
5,000,000 operations
20 ms
2500 V(rms)
2500 V(rms)
-40 – +85 °C (-40 – +185 °F)
-40 – +55 °C (-40 – +131 °F)
3 g-n at 10-55 Hz
10 g-n
IP 40
88 g (3 .10 oz)
UL with socket, UR (E43641), CE, CSA (LR40787),
RoHS
Note: Actual product performance may vary depending on application and environmental conditions.
30