Battery capacities and floor loading for the standard rack systems
19" rack system without batteries
Battery model
TLX 8O
TLX 100
TLX 150
TLX 180
48 V [kg]
104
113
127
132
Rack weight without batteries
48 V [lbs] 24 V [kg] 24 V [lbs]
230
122
270
250
132
290
280
145
320
290
150
330
W [cm]
52
52
52
52
W [in]
20.5
20.5
20.5
20.5
D [cm]
42
52
71
85
D [in]
16.5
20.5
28.0
33.5
Rack dimensions
H [cm]
H [in]
213
84
213
84
213
84
213
84
19" rack system with batteries
Battery model
Rack weight with batteries
48 V [kg] 48 V [lbs]
506
1115
581
1280
814
1795
934
2060
24 V [kg] 24 V [lbs]
524
1155
599
1320
832
1835
953
2100
Number of strings
48 V
5
5
5
5
24 V
10
10
10
10
C
8
Ah/
string
75
97
140
172
Max Wh/
string
18000
23280
33600
41280
Floor
loading
[kg/m
2
]
2400
2208
2248
2150
Floor
loading
[lbs/ft
2
]
492
452
460
440
TLX 8O
TLX 100
TLX 150
TLX 180
The floor loading data is calculated based on the full system load.
23" rack system without batteries
Battery model
TLX 8O
TLX 100
TLX 150
TLX 180
48 V [kg]
109
118
132
136
Rack weight without batteries
48 V [lbs] 24 V [kg] 24 V [lbs]
240
127
280
260
136
300
290
150
330
300
154
340
W [cm]
62
62
62
62
W [in]
24.5
24.5
24.5
24.5
D [cm]
38
42
57
68
D [in]
15.0
16.5
22.5
26.7
Rack dimensions
H [cm]
H [in]
213
84
213
84
213
84
213
84
23" rack system with batteries
Battery model
Rack weight with batteries
48 V [kg] 48 V [lbs]
517
1140
624
1375
821
1810
930
2050
24 V [kg] 24 V [lbs]
535
1180
642
1415
839
1850
948
2090
Number of strings
48 V
5
5
5
5
24 V
10
10
10
10
C
8
Ah/
string
75
97
140
172
Max Wh/
string
18000
23280
33600
41280
Floor
loading
[kg/m
2
]
2258
2460
2360
2246
Floor
loading
[lbs/ft
2
]
462
504
483
460
TLX 8O
TLX 100
TLX 150
TLX 180
The floor loading data is calculated based on the full system load.
Notes
1. Use provided information to insure proper floor loadings are respected. Review building codes and respect proper engineering practices
before installing the battery rack systems. Always consider fully loaded battery rack systems when evaluating floor loadings.
2 Anchoring mechanism and grounding straps are not provided with the rack systems. Anchoring and grounding shall be done in
accordance with all applicable and required company as well as local, state and federal codes.
3. Saft is not liable or responsible for the improper installation of the rack systems.
Saft
Industrial Battery Group
12, rue Sadi Carnot
93170 Bagnolet - France
Tel. : +33 1 49 93 19 18
Fax : +33 1 49 93 19 64
www.saftbatteries.com
Doc. No 21808-2-0811
Information in this document is subject to change without notice
and becomes contractual only after written confirmation by Saft.
Published by the Communications Department.
Photo credit: Saft
Société par Actions Simplifiée au capital de 31 944 000 €
RCS Bobigny B 383 703 873
Produced in the UK by Arthur Associates Limited