FCP600-48 AC-DC Front End Data Sheet
48V Output, 600 Watts
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings may cause performance degradation, adversely effect long-
term reliability, and cause permanent damage to the converter.
Parameter
Input Voltage
Conditions/Description
Min
Max
264
300
Units
VAC
VAC
Continuous
Transient, 60 ms
Operating Temperature
Storage Temperature
Ambient
0
55
°C
Vi min-Vi max, Io nom, cooling by internal fan
Non-operational
-40
85
°C
Environmental, Mechanical, & Reliability Specifications
All specifications apply over specified input voltage, output load and temperature range, unless otherwise noted.
Parameter
Operating Humidity
Storage Humidity
Shock
Conditions/Description
Relative humidity, non-condensing
Relative humidity, non-condensing
IEC/EN 60068-2-27, 11 ms
Min
10
5
Nom
Max
90
Units
%
95
%
30
gn
Sinusoidal Vibration
IEC/EN 60068-2-6
2-8 Hz
7.5
2
mil
gn
8-200 Hz
200-500 Hz
4
gn
MTBF
MIL-HDBK-217F Notice 2, GB, 25 °C
TBD
kh
Isolation Specifications
The electric strength test is performed in the factory as routine test in accordance with EN 550116, IEC/EN 60950,
and UL 1950 and should not be repeated in the field. Power-One will not honor any warranty claims resulting from
electric strength field tests.
Parameter
Conditions/Description
Min
Nom
Max
Units
Insulation Safety Rating
Input/Case
Input/Output
Output/Case
Basic
Reinforced
Functional
Electric Strength Test Voltage
Input/Case
Input/Output
Output/Case
2.121
3.6
0.5
kVDC
kVDC
kVDC
OCT 30, 2006 revised to NOV 10, 2006
Page 2 of 6