ABC400-10XXG Data Sheet
Voltage Dips and Interruptions
Magnetic Fields
EN 61000-4-11
EN 61000-4-8
C
A
9.2 EMISSION
Test
Conducted Emission
Radiated Emission
Harmonic Emissions
Voltage Fluctuation and Flicker
Canadian Communications Radio
Interference
Rules for Unintentional Radiations
Taiwan EMI Regulations
Standard / Description
EN55022 / CISPR 22: 0.15 … 30 MHz, QP and AVG,
single unit
EN55022 / CISPR 22: 30 MHz … 1 GHz, QP,
single unit
IEC61000-3-2, Vin = 100 VAC/ 60 Hz, 100% Load
IEC61000-3-2, Vin = 240 VAC/ 50 Hz, 100% Load
EN61000-3-3
ICES-003
FCC Part 15, Sub Part-B
BSMI: CNS 13438 (95)
Criteria
Class A
6 dB Margin
Class A
6 dB Margin
Class A
Class A
PASS
NA
NA
NA
10 SAFETY / APPROVALS
Maximum electric strength testing is performed in the factory according to IEC/EN 60950, and UL 60950. input-to-output electric
strength tests should not be repeated in the field. Power-One will not honor any warranty claims resulting from electric strength
field tests.
Parameter
Description / Conditions
UL 60950-1 Second Edition
CSA-C22.2 No. 60950-1-03 Second Edition
IEC 60950-1:2005
Agency Approvals
EN 60950-1:2006
CE Mark for LVD
CB Approval
Input / Case
Insulation Safety Rating Input / Output
Output / Case
Primary (L/N) to protective earth (PE)
Creepage / clearance
Primary to secondary
Input to case
Electrical strength test Input to output
Output and Signals to case
Min
Nom
Max
Unit
Approved by
independent body
(see CE Declaration)
Basic
Reinforced
Functional
According to
safety standard
2121
4242
500
mm
mm
VDC
VDC
VDC
d
C
Rev. AA1, 19-May-2011
Page 10 / 13