DATA SHEET
Notes:
1.
2.
3.
4.
5.
6.
7.
8.
Combined power from main output, Vfan and Vs/b should not exceed total power rating.
Fan output tolerance is ± 20%. When V1 full load, Vfan needs 20 mA load to be within regulation specification. Peak
current for fan output is 1 A.
Ripple is 2% up to 20% load and less than 1% above 20% load. Output noise measurement is made with a 20 MHz
bandwidth using a 6” twisted pair, terminated with a 10 uF tantalum capacitor in parallel with a 0.1 uF ceramic capacitor.
Specifications are for nominal input voltage, 25° C and max load unless otherwise stated.
Air flow over length of supply recommended (either direction) for forced air rating.
Class 1 models have Earthing tab J4. Class 2 models (-2 suffix) have no Earthing tab.
Specifications may change without notice.
Warranty 2 years.
General Specifications
PARAMETER
Hold Up Time
MTBF
Switching Frequency
Isolation Voltage
Weight
DESCRIPTION/CONDITION
120 Vac
230 Vac
>200 kHrs
PFC converter variable 35 to 250 kHz, 90
kHz typical
Input to Output: Min 4242 Vdc
325 g (0.72 lbs)
10 mSec
10 mSec
Bellcore TR-332
Resonant converter variable 35 to 250 kHz,
90 kHz typical
Environmental
PARAMETER
Operating Temperature
Altitude
Storage Temperature
Humidity
Conducted emissions:
Radiated Emissions
Static Discharge
Harmonic Current
DESCRIPTION/CONDITION
-20 to 70° C
Operating 10,000 ft.
-40 to +70° C
95%
EN55022, FCC part 15 Level B
EN55022, FCC part 15 Level B
EN61000-4
EN61000-3-2, Class D
To be controlled in end system
2, 3, 4, 5 Level 3
Non-Condensing
See derating charts below
Non-operation 40,000 ft.
Signals
PARAMETER
Power Good Signal
Power Fail Signal
Remote ON / OFF
Remote Sense
DESCRIPTION/CONDITION
TTL signal goes high after main output is in regulation band. Delay is 0.1 to 0.3 sec.
TTL signal goes low 1 msec advance before output goes out of regulation due to mains failure
To turn-on power supply short J3 pin 4 to pin 6 (PSU is shipped in this configuration)
Compensates for 200 mV cable drop
Safety
PARAMETER
EN / UL / CSA
DESCRIPTION/CONDITION
EN60950-1+A12:2011, IEC60950-1 2
nd
+A1 2009, CSA-22.2 No 60950-01-07+ A1, UL60950-
1-2011
BCD.00284_AA_May-31-2013
3