Module no:0531207 LabelId:0531207 Operator:Phoenix
Technical data
Dimensions
Width / length
Height (NS 35:7.5 / NS 35:15 / NS 32)
Technical data in accordance with IEC 60
947-7-1
Maximum load current / cross section
Max. cross section with insertion bridge (solid
/ stranded)
Rated surge voltage / contamination class
Surge voltage category / insulation material
group
Connection capacity
Stranded with ferrule with / without plastic
sleeve
[mm ]
2
14:45:20, Donnerstag, 28. Juni 2001
[mm]
[mm]
6.2 / 42.5
47 / 54.5 / 52
[A] / [mm ]
[mm ]
[kV] / –
–/–
2
2
32 / 4
4 / 2.5
8/3
III / I
0.25 - 4 / 0.25 - 4
Multi-conductor connection (2 conductors with same
cross section)
Solid / stranded
Stranded with ferrule without plastic sleeve
Stranded with TWIN ferrule with plastic sleeve
Stripping length
Internal cylindrical gage (IEC 60
947-1:1988)
Thread
Torque
Insulation material
Inflammability class acc. to UL 94
Temp. indices RTI acc. to UL 746 B / Ti acc. to IEC 60
216-1
Installation temperature range / temperature
class
1
[mm ]
[mm ]
[mm ]
[mm]
2
2
2
0.2 - 1.5 / 0.2 - 1.5
0.25 - 1.5
0.5 - 1.5
9
A3
M3
[Nm]
0.6 - 0.8
PA
V2
125 / 100
-40...+80 / T6
[°C] / –
) The max. nominal voltage is determined by the mounting rails, at
4
418 V.
Important Ex note:
If the fixed bridges and chain bridges are used, a partition plate is necessary between bridges which make direct
contact, and a cover is required at the beginning and end of each bridge.
Accordingly, equipotential bondings that were created with insertion bridges must be separated by means of partition
plates.
If the fixed bridges FB 150 are used for bridging of non-adjacent terminals, the max. nominal voltage is reduced to 275
V.
If these elements are mixed with other series and sizes and if other accessories are used, the required air and creepage
distances must be complied with.
Phoenix Contact Elektronischer Katalog
Page 2 / 2