Accessories (Order Separately)
Name
Specifications
Remarks
Model
Memory Cassette EEPROM (for data
security and copying)
Enables programs and parameter settings to be saved or copied to another
ZEN. (See note 1.)
ZEN-ME01
LCD-type CPU Unit with LED-type CPU Unit without
display (See note 2.)
display (See note 3.)
Transfer from ZEN to
Memory
Supported
Not supported
Transfer from Memory Supported
Cassette to ZEN
Automatic transfer when
power turned ON
Memory Cassette
initialization
Supported
Not supported
Connecting Cable 2 m RS-232C (9-pin D-
sub connector)
---
ZEN-CIF01
Battery Unit
10 years min. Battery life Ladder programs and parameter settings are saved to the CPU Unit EEP-ROM ZEN-BAT01
(at 25°C)
but calendar, clock, and holding timer bits and holding timer/counter present
values are held by the capacitor. Therefore, if the power supply is interrupted
for 2 days or more (at 25°C), this data will be reset. Use a Battery Unit for
systems where the power supply may be interrupted for long periods.
ZEN Support
Software
Runs on Windows 95, 98, Specifically designed for the ZEN (CD-ROM).
2000, ME, XP, or NT 4.0.
ZEN-SOFT01-V4
Note: 1. Memory Cassettes created using a CPU Unit can be read to other CPU Units, regardless of which model is used. Restrictions, apply, however, to
the functions that can be used, depending on the CPU Unit version combination. For details, refer to “Memory Cassette and CPU Unit
Combinations” on page 33.
2. Standard LCD-type, Economy-type, and Communications-type CPU Units (i.e., excluding ZEN-@C2@@-@-V2 models).
3. LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).
Mounting Accessories (Order Separately)
Name
Specifications
Model
Mounting Track
50 cm (l) × 7.3 mm (t) PFP-50N
1 m (l) × 7.3 mm (t)
1 m (l) × 16 mm (t)
PFP-100N
PFP-100N2
PFP-M
End Plate
Spacer
PFP-S
System Configuration
Expansion I/O Units
Power Supply Unit
CPU Unit
Battery Unit
Connecting Cable
Memory Cassette
Support Software
Note: 1. Up to 3 Expansion I/O Units can be connected to any type of CPU Unit except for Economy-type CPU Units. Expansion I/O Units with AC Inputs,
however, cannot be connected to CPU Units with DC Power Supplies.
2. The Connecting Cable and Memory Cassette cannot be connected to the ZEN at the same time.
3. Programs cannot be written to LED-type CPU Units (i.e., ZEN-@C2@@-@-V2 models) without the ZEN Support Software or a Memory Cassette.
6
Programmable Relay ZEN V2 Units