Error Messages and Alarm Outputs  
Section 5-1  
Non-fatal Errors (cont’d)  
Item  
RUN  
Auxiliary Area data  
Error data  
Corrective action  
output Error flags  
Error  
code  
System error (FAL)  
JMP error  
ON  
A40215 ON A430 to A461 (Executed 4101  
Check the program.  
FAL Number)  
-42FF  
(*)  
ON  
A40213 ON None  
A40212 ON None  
00F9  
00F8  
Check and correct the program.  
Indirect DM BCD er- ON  
ror  
Non-fatal SFC error  
ON  
A40211 ON A418 (SFC Non-fatal Er- 00F4  
ror Code)  
I/O verification error  
ON  
A40209 ON None  
00E7  
Verify the I/O table. After the cor-  
rective actions have been taken,  
create a new I/O table.  
CPU Bus Unit error  
ON  
ON  
A40207 ON A422 (CPU Bus Unit Er- 0020-  
Check the Unit.  
ror Unit Number)  
A42315 ON (CPU Bus  
Link Error Flag)  
0215  
0231  
(**)  
SYSMAC BUS/2 er-  
ror  
A40206 ON A424 (SYSMAC BUS/2  
Error Master Number)  
00B0-  
00B3  
Check transmission lines for SYS-  
MAC BUS/2. Check to see if  
A480 to A499 (SYSMAC (***)  
SYSMAC BUS/2 Slave is normal.  
BUS/2 Error Unit Num-  
ber)  
SYSMAC BUS error ON  
A40205 ON A425 (SYSMAC BUS  
Error Master Number)  
00A0-  
00A7  
Check transmission lines for SYS-  
MAC BUS. Check to see if SYS-  
MAC BUS Slave is normal.  
A470 to A477 (SYSMAC (****)  
BUS Error Codes)  
Battery failure  
ON  
A40204 ON A42615 (PC Battery Low 00F7  
Replace the battery of the CPU or  
Memory Card. Check the connec-  
tions of the CPU battery.  
Flag)  
A42614 (Memory Card  
Battery Low Flag)  
CPU Bus Unit setting ON  
error  
A40203 ON A427 (CPU Bus Unit Pa- 0400-  
rameter Error Unit Num- 0415  
ber)  
Check the Unit.  
Momentary power in- ON  
terruption  
A40202 ON A012 to A013 (Power In- 0002  
terruption Time)  
Check the supply voltage and  
Power Supply Unit wiring.  
A014 (Number of Power  
Interruptions)  
Output inhibit  
ON  
ON  
A00015 ON None  
--- None  
---  
---  
Turn OFF A00015.  
Host link communi-  
cation  
Release memory protection.  
Note * 101 through 2FF indicate FAL Nos.  
** 00 through 15 indicate the Unit Nos. of the CPU Bus Units. 31 indicates a CPU  
bus link error.  
*** 0 through 3 indicate the RM addresses of SYSMAC BUS/2.  
**** 0 through 7 indicate the RM addresses of SYSMAC BUS.  