 浏览型号3G5A2-OC221-PE的Datasheet PDF文件第8页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第9页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第10页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第11页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第13页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第14页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第15页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第16页  
Conformance to EC Directives  
6
4. PCs complying with EC Directives also conform to the Common Emission  
Standard (EN50081-2). When a PC is built into a machine, however, noise  
can be generated by switching devices using relay outputs and cause the  
overall machine to fail to meet the Standards. If this occurs, surge killers  
must be connected or other measures taken external to the PC.  
The following methods represent typical methods for reducing noise, and  
may not be sufficient in all cases. Required countermeasures will vary  
depending on the devices connected to the control panel, wiring, the config  
-
uration of the system, and other conditions.  
Countermeasures  
Refer to EN50081-2 for more details.  
Countermeasures are not required if the frequency of load switching for the  
whole system including the PC is less than 5 times per minute.  
Countermeasures are required if the frequency of load switching for the whole  
system including the PC is 5 or more times per minute.  
Countermeasure Examples  
When switching an inductive load, connect a surge protector, diodes, etc., in par  
-
allel with the load or contact as shown below.  
Circuit  
CR method  
Current  
Characteristic  
Required element  
AC  
DC  
Yes  
Yes  
If the load is a relay or solenoid, there The capacitance of the capacitor must  
is a time lag between the moment the be 1 to 0.5 µF per contact current of  
circuit is opened and the moment the  
load is reset.  
1 A and resistance of the resistor must  
be 0.5 to 1 per contact voltage of  
1 V. These values, however, vary with  
the load and the characteristics of the  
relay. Decide these values from  
testing, and take into consideration  
that the capacitance suppresses spark  
discharge when the contacts are  
separated and the resistance limits  
the current that flows into the load  
when the circuit is closed again.  
If the supply voltage is 24 or 48 V,  
insert the surge protector in parallel  
with the load. If the supply voltage is  
100 to 200 V, insert the surge  
Power  
supply  
protector between the contacts.  
The dielectric strength of the capacitor  
must be 200 to 300 V. If the circuit is  
an AC circuit, use a capacitor with no  
polarity.  
Diode method  
No  
Yes  
The diode connected in parallel with  
the load changes energy accumulated of the diode must be at least 10 times  
The reversed dielectric strength value  
by the coil into a current, which then  
flows into the coil so that the current  
will be converted into Joule heat by  
the resistance of the inductive load.  
as large as the circuit voltage value.  
The forward current of the diode must  
be the same as or larger than the load  
current.  
Power  
supply  
This time lag, between the moment  
the circuit is opened and the moment  
the load is reset, caused by this  
method is longer than that caused by  
the CR method.  
The reversed dielectric strength value  
of the diode may be two to three times  
larger than the supply voltage if the  
surge protector is applied to electronic  
circuits with low circuit voltages.  
Varistor method  
Yes  
Yes  
The varistor method prevents the  
imposition of high voltage between the  
contacts by using the constant voltage  
characteristic of the varistor. There is  
time lag between the moment the  
circuit is opened and the moment the  
load is reset.  
---  
Power  
supply  
If the supply voltage is 24 or 48 V,  
insert the varistor in parallel with the  
load. If the supply voltage is 100 to  
200 V, insert the varistor between the  
contacts.  