 浏览型号3G5A2-OC221-PE的Datasheet PDF文件第102页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第103页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第104页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第105页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第107页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第108页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第109页浏览型号3G5A2-OC221-PE的Datasheet PDF文件第110页  
Error Processing and Correction  
Section 5-3  
Input Units  
Symptom  
Cause  
Remedy  
Not all inputs turn ON or in-  
dicators are not lit.  
(1) Power is not supplied to Input Unit.  
(2) Supply voltage is low.  
Supply power  
Adjust supply voltage to within rated range.  
Tighten screws.  
(3) Terminal block mounting screws are  
loose.  
(4) Faulty contact of terminal block con-  
nector.  
Replace terminal block connector.  
Replace Unit.  
Not all inputs turn ON (indi-  
cator lit).  
Input circuit is faulty.  
Not all inputs turn OFF.  
Input circuit is faulty.  
Replace Unit.  
Specific bit does not turn  
ON.  
(1) Input device is faulty.  
Replace input devices.  
Check input wiring  
(2) Input wiring disconnected.  
(3) Terminal block screws are loose.  
Tighten screws  
(4) Faulty terminal block connector con-  
tact.  
Replace terminal block connector.  
(5) Too short ON time of external input.  
(6) Faulty input circuit  
Adjust input device  
Replace Unit.  
(7) Input bit number is used for output in-  
struction.  
Correct program.  
Specific bit does not turn  
OFF.  
(1) Input circuit is faulty.  
Replace Unit.  
(2) Input bit number is used for output in-  
struction.  
Correct program.  
Input irregularly turns ON/  
OFF.  
(1) External input voltage is low.  
Adjust external input voltage to within rated  
range.  
(2) Malfunction due to noise.  
Protective measures against noise, such  
as:  
(1) Install surge suppressor.  
(2) Install insulation transformer.  
(3) Install shielded cable.  
(3) Terminal block screws are loose.  
Tighten screws  
(4) Faulty terminal block connector con-  
tact.  
Replace terminal block connector.  
Error occurs in units of 8  
points.  
(1) Common terminal screws are loose.  
Tighten screws  
(2) Faulty terminal block connector con-  
tact.  
Replace terminal block connector.  
(3) Faulty data bus  
(4) Faulty CPU  
Faulty indicator  
Replace Unit.  
Replace CPU.  
Replace Unit.  
Input indicator is not lit in  
normal operation.  
93  