Preparing for Operation
Chapter 4
Note 2. The DIP switch is located inside the Inverter. Use this switch to change the set-
ting when frequency references are to be input in terms of amperage (4 to 20
mA). For details, refer to Section 7-2 Frequency Reference by Amperage Input.
For voltage input, never set the DIP switch to ON. Doing so may damage the
equipment.
Interruption Mode Selection
n03
Setting range 0, 1
Factory setting 0
This constant is used to specify the interruption mode when the STOP/RESET Key is
pressed or the operation command is OFF.
Value
Description
0
1
Frequency deceleration stop
Free running
Example of Frequency Deceleration Stop
Deceleration time 1
(n21)
Minimum output frequency determined
with constant set in n29: Factory-set to
1.5 kHz
Output frequency
Time
Interruption DC control time determined
with constant set in n47: Factory-set to 0.5
second
Forward rotation
(Reverse rotation)
ON
OFF
Operation command
Example of Free Running
Inertia of motor
Output frequency
Time
Forward rotation
(Reverse rotation)
ON
OFF
Operation command
Note This constant is available for models with a PROM number (software version) of
“200” or higher.
4-13