Preparing for Operation  
Chapter 4  
Note 2. The DIP switch is located inside the Inverter. Use this switch to change the set-  
ting when frequency references are to be input in terms of amperage (4 to 20  
mA). For details, refer to Section 7-2 Frequency Reference by Amperage Input.  
For voltage input, never set the DIP switch to ON. Doing so may damage the  
equipment.  
Interruption Mode Selection  
n03  
Setting range 0, 1  
Factory setting 0  
This constant is used to specify the interruption mode when the STOP/RESET Key is  
pressed or the operation command is OFF.  
Value  
Description  
0
1
Frequency deceleration stop  
Free running  
Example of Frequency Deceleration Stop  
Deceleration time 1  
(n21)  
Minimum output frequency determined  
with constant set in n29: Factory-set to  
1.5 kHz  
Output frequency  
Time  
Interruption DC control time determined  
with constant set in n47: Factory-set to 0.5  
second  
Forward rotation  
(Reverse rotation)  
ON  
OFF  
Operation command  
Example of Free Running  
Inertia of motor  
Output frequency  
Time  
Forward rotation  
(Reverse rotation)  
ON  
OFF  
Operation command  
Note This constant is available for models with a PROM number (software version) of  
“200” or higher.  