Design  
Chapter 3  
Determining the Wire Size  
Determine the wire size for the main circuit so that line voltage drop is within 2% of the  
rated voltage.  
Line voltage drop VD is calculated as follows:  
VD (V) = p3 x wire resistance (/km) x wire length (m) x amperage (A) x 10–3  
H Wiring on the Input Side of Main Circuit  
D Installing a Molded-case Circuit Breaker  
Always connect the power input terminals (R, S, and T) and power supply via a molded-  
case circuit breaker. Power must be supplied instantaneously. Unstable power startup  
will not start the Inverter.  
D Installing a Ground Fault Interrupter  
If a ground fault interrupter is to be connected to the wire on the primary side (R, S, and  
T) of the main circuit, use either of the following interrupters to prevent malfunctions:  
Ground fault interrupter with a sensitivity amperage of 200 mA or more and with an  
operating time of 0.1 second or more  
Ground fault interrupter with high-frequency countermeasures (for Inverter)  
D Installing a Magnetic Contactor  
This Inverter can be used without a magnetic contactor (MC) on the power supply side.  
If the power supply for the main circuit is to be shut off because of the sequence, a mag-  
netic contactor can be used instead of a molded-case circuit breaker.  
However, when a magnetic contactor is installed on the primary side of the main circuit  
to forcibly stop a load, note that regenerative braking does not work and the load coasts  
to a stop.  
A load can be started and stopped by opening and closing the magnetic contactor on  
the primary side. Note, however, that frequently opening and closing the magnetic  
contactor may cause the Inverter to break down.  
When the Inverter is operated with a Digital Operator, automatic operation cannot be  
performed after recovery from a power interruption.  
D Connecting Input Power Supply to the Terminal Block  
Because the phase sequence of input power supply is irrelevant to the phase sequence  
(R, S, T) of the terminal block, input power supply can be connected to any terminal on  
the terminal block.  
3-12  