Appendix A
Chapter 7
Constant Indi-
Description
Setting range
0.0 to 999 (seconds)
Setting
[10.0]
no.
cators
n21
Deceleration
time
n24
n25
n26
Maximum
frequency
50.0 to 400 (Hz)
[60.0]
Maximum
voltage
1 to 255 (V) (see note 1)
1.6 to 400 (Hz)
[200]
Maximum
voltage
[60.0]
frequency (basic
frequency)
n31
Electronic
thermal
0.0 to 120% of rated Inverter amperage
Specify the rated motor amperage.
reference
current
n33
n36
Stall prevention
during
deceleration
0: Stall prevention
1: No stall prevention
Operation after
recovery from
power
0: Discontinues operation.
1: Continues operation only if the power
interruption is within 0.5 second.
2: Continues operation unconditionally.
1: 2.5 (kHz) (see note 2)
2: 5 (kHz)
interruption
n37
Carrier
frequency
3: 7.5 (kHz)
4: 10 (kHz)
n39
n40
n61
n64
Frequency
reference gain
0.10 to 2.00 (times)
[1.00]
[0]
Frequency
reference bias
–99 to 99 (%)
Stop Key
selection
0, 1
0, 1
[0]
Operator’s
frequency
[0]
setting method
Note 1. The upper limit of setting range and the factory settings for the 400-VAC-class
Inverters are double the above values.
Note 2. The setting range of the 400-VAC-class Inverter is “1 to 5.” The factory setting of
the 3G3EV-A4015M-CUE is “3.”
Note 3. Values in shaded sections or values in brackets represent factory settings.
7-11