Specifications
Chapter 6
H Operation Specifications
Three photocoupler input terminals (24 VDC, 8 mA)
Control input
• Forward/stop [SF]
• Reverse/stop [SR]
• Multi-function input [S1] (set in constant No. 06)
Select either of “fault reset,” “external fault,” and “multi-step
speed command.”
Note When 3-wire sequence mode (constant No. 01 = “9”) is se-
lected, the terminals become as follows:
• Run command [SF]
• Stop command [SR]
• Forward/reverse rotation command [S1]
One analog input terminal (0 to 10 VDC or 4 to 20 mA)
• Frequency reference input [Between FC and FR]
Control output
One SPDT relay contact output terminal [MA, MB]
(30 VDC and 1A; 250 VAC and 1A)
• Multi-function contact output (set in constant No. 09)
Select either of “fault occurrence,” “operation in progress,” and
“frequency matching.”
6-6