Design
Chapter 3
D Three-phase 400-VAC Input Model
3G3EV
model
Output
W
H
D
W1
H1
118
Weight
(kg)
108
128
96
0.2 kW
0.4 kW
0.75 kW
1.5 kW
92
Approx. 1.0
Approx. 1.0
Approx. 1.5
Approx. 2.0
A4002(-j)
A4004(-j)
A4007(-j)
A4015(-j)
110
140
170
130
118
3-1-2 Installation Conditions
H Installation Site
• Install the Inverter under the following conditions:
Ambient temperature for operation: –10°C to 50°C
Humidity: 90% RH or less (non-condensing)
• Install the Inverter in a clean location free from oil mist and dust. Alternatively, install it
in a totally enclosed panel that is completely shielded from suspended dust.
• When installing or operating the Inverter, always take special care so that metal pow-
der, oil, water, or other foreign matter do not get in the Inverter.
• Do not install the Inverter on inflammables such as wood.
H Direction of Installation
• Install the Inverter on a vertical surface so that the characters on the nameplate are
oriented upward.
H Installation Space
• When installing the Inverter, always provide the following installation space to allow
normal heat dissipation from the Inverter:
100 mm min.
100 mm min.
W= 30 mm min.
Air
Side
Air