Design
Chapter 3
D Control Circuit Terminal Connections
Multi-function contact
output (Contact a)
Forward/Stop
Reverse/Stop
Clamp core
(Contact b)
Common
S1 to S3
Multi-function input
Sequence input common
Multi-function
photocoupler output
Multi-function
photocoupler output
common
Clamp
core
Frequency reference adjuster
Frequency reference
power supply (12 V)
Multi-function analog output
Voltmeter
Frequency reference
input
Frequency reference
input common
Multi-function analog
output common
(2 kΩ, 1/4 W min.)
Note 1. The standard model does not have the S2, S3, PA, PC, AM, or AC terminal.
Note 2. The sequence input and the sequence output can be wired with a single shielded cable.
3-2-2 Wiring Around the Main Circuit
System reliability and noise resistance are affected by the wiring method used. There-
fore, always follow the instructions given below when connecting the Inverter to periph-
eral devices and other parts.
H Wire Size
For the main circuit and ground, always use 600-V polyvinyl chloride (PVC) cables.
If the cable is long and may cause voltage drops, increase the wire size according to the cable length.
2
Model
3G3EV-A2001(M)-CUE
3G3EV-AB001(M)-CUE
Terminal symbol
R S T B1 B2
Terminal screw
M3.5
Wire size (mm )
0.75 to 2
U V W
R S T B1 B2
U V W
M3.5
M3.5
M3.5
M3.5
0.75 to 2
0.75 to 2
0.75 to 2
3G3EV-A2002(M)-CUE
3G3EV-AB002(M)-CUE
3G3EV-A4002(M)-CUE
3G3EV-A2004(M)-CUE
3G3EV-AB004(M)-CUE
3G3EV-A4004(M)-CUE
3G3EV-A2007(M)-CUE
3G3EV-AB007(M)-CUE
3G3EV-A4007(M)-CUE
3G3EV-A2015(M)-CUE
3G3EV-AB015(M)-CUE
3G3EV-A4015(M)-CUE
R S T B1 B2
U V W
R S T B1 B2
U V W
R S T B1 B2
U V W
1.25 to 2
0.75 to 2
Note Tighten the M3.5 terminal screw to the torque of 0.8 N S m.
3-11