Design
Chapter 3
D Three-phase 400-VAC Input Model
3G3EV model
A4002(M)-CUE
A4004(M)-CUE
A4007(M)-CUE
A4015(M)-CUE
Output
0.2 kW
W
H
D
W1
H1
Weight (kg)
Approx. 1.0
Approx. 1.0
Approx. 1.5
Approx. 2.0
108
128
96
118
92
0.4 kW
0.75 kW
1.5 kW
110
140
170
130
118
3-1-2 Installation Conditions
H Installation Site
• Install the Inverter under the following conditions:
Ambient temperature for operation: –10°C to 50°C
Humidity: 90% RH or less (non-condensing)
• Install the Inverter in a clean location free from oil mist and dust. Alternatively, install it in a totally en-
closed panel that is completely shielded from suspended dust.
• When installing or operating the Inverter, always take special care so that metal powder, oil, water, or
other foreign matter do not get in the Inverter.
• Do not install the Inverter on inflammables such as wood.
H Direction of Installation
• Install the Inverter on a vertical surface so that the characters on the nameplate are oriented upward.
H Installation Space
• When installing the Inverter, always provide the following installation space to allow normal heat dis-
sipation from the Inverter:
100 mm min.
W= 30 mm min.
Air
Side
Air
100 mm min.
3-4