Power Supply Units
Section 3-4
3-4-3 Wiring Other Terminals
The Power Supply Units provide a START input and a RUN output. These termi
-
nals can be used to help control system operation.
Power supply
START input (CPU Racks only)
24 V,10 mA
To system con
trol circuits
-
RUN output (all Racks)
Maximum Switching Capacity:
250 VAC: 2 A (resistive load, cosf = 1)
Emergency
stop circuit
250 VAC: 0.5 A (inductive load, cos
24 VDC: 2 A
f = 0.4)
Note 1. Use reinforced insulation or double insulation on the DC power supply con
nected to CV500-PS211 Power Supply Unit when complying with EC direc
tives (low voltage).
-
-
2. The maximum switching capacity of the CV500-PS211 Power Supply Unit is
A at 24 VDC when complying with EC Directives (low-voltage directives).
2
START Input
The START input terminals are short-circuited at the factory with a short bar. The
short bar can be removed and the terminals wired to a 10-mA, 24-VDC external
input to control PC operation. When these terminals are open, PC operation will
stop.
RUN Output
The RUN output terminals will be ON (closed) when the PC is operating in RUN
or MONITOR mode. These terminals can thus be wired to provide an external
signal indicating the operating status of the PC, such as is used in the emergen
-
cy stop circuit in the next section.
55