Mounting Racks
Section 3-3
When mounting the PC in a control panel, mount the Racks to an intermediate
plate. Holes for mounting the Racks to the intermediate plate should be drilled at
intervals shown in the following diagram. Completely ground the intermediate
mounting plates. Use conductor-plated plates to improve noise immunity.
L
Four, M5
CPU Backplane
CV500-BC101/051/031
CVM1-BC103/053
250
150ꢀ0.5
170 to 220
150ꢀ0.5
70 to 120
Expansion CPU Backplane
Expansion I/O Backplane
CV500-BI111/112/062/042
CVM1-BI114/064
250
Four, M5
W
Model
W
Lꢀ0.5
CV500-BC101/BI111/112
CVM1-BC103/BI114
480
306
236
465
CV500-BC051/BI062
CVM1-BC053/BI064
291
221
CV500-BC031/BI042
3-3-1 Duct Work
If power cables carrying more than 10 A at 400 V or 20 A at 220 V must be run
parallel to I/O wiring, leave at least 300 mm between the power cables and the
I/O wiring, as shown in the following diagram.
Low current cables
1
300 mm min.
Control cables
2
300 mm min.
Power cables
3
Grounding at resistance
of less than 100 W
1 = I/O wiring
2 = General control wiring
3 = Power cables
49