Racks  
Section 2-2  
Note The Units in the following table can be mounted to the CV500-BC101 CPU Back  
-
plane if a CV500-ICjjj I/O Control Unit and CV500-IIjjj I/O Interface Unit  
are used. If an I/O Control Unit is not used, only one Expansion I/O Rack can be  
connected and a total of eight Units maximum can be mounted to the PC regard  
-
less of the Rack to which they are mounted.  
Name  
Model  
3G2A5-ADjjj, C500-AD101  
3G2A5-CTjjj, C500-CT041  
3G2A5-DAjjj, C500-DA101  
C500-FZ001  
Analog Input Unit  
High-speed Counter Unit  
Analog Output Unit  
Fuzzy Logic Unit  
ID Sensor Unit  
C500-IDSjj/-IDS01-V1  
C500-LDP01-V1  
Ladder Program I/O Unit  
Position Control Unit  
3G2A5-NC103-E/-NC111-EV1,  
C500-NC222-E  
SYSMAC BUS Optical Remote I/O  
Master Unit  
3G2A5-RM001-PEV1/-RM001-EV1,  
C500-RM201  
ASCII Unit  
C500-ASC04  
C500-CP131  
Cam Positioner Unit  
Magnetic Card Reader Unit  
PID Control Unit  
3G2A5-MGC01  
3G2A5-PID01-E  
2-2-2 Expansion CPU Racks  
An Expansion CPU Rack can be provided to increase the mounting space for  
CPU Bus Units. The Expansion CPU Rack is connected directly to the CPU  
Rack. Two cables are required to connect the Expansion CPU Rack to the CPU  
Rack, a CPU Bus Cable and an I/O Connecting Cable. If either of these connec  
-
tions is broken, the system will be disabled  
Only one Expansion CPU Rack can be connected to the CPU Rack. T  
o further  
increase the number of I/O Units, a series of Expansion I/O Racks may be con  
-
nected to the Expansion CPU Rack or to the I/O Control Unit on the CPU Rack. If  
no Expansion I/O Rack is connected to the I/O Interface Unit, connect a Termina-  
tion Resistance Unit to the unused connector on the I/O Interface Unit.  
CPU Bus Connector Connects the Expansion CPU Rack to the CPU Rack.  
I/O Connector Connects the Ex-  
pansion CPU Rack to the CPU  
Rack.  
Expansion CPU  
Backplane  
CV500-BI111  
T
ermination Resistance Unit  
A Termination Resistance Unit  
must be connected to the unused  
I/O cable connector when an Ex  
-
pansion I/O Rack is not connected.  
Power Supply Unit  
CV500-PS221/PS211  
CVM1-PA208  
I/O Connector Connects the Ex-  
pansion CPU Rack to an Expan  
sion I/O Rack. When not used,  
connect a Termination Resistance  
Unit.  
-
I/O Interface Unit (CV500-II101)  
Connects the Expansion CPU  
Rack to the CPU Rack and, if nec-  
essary, to an Expansion I/O Rack.  
Units  
(Up to 11 or the following Units: SYSMAC NET Link  
Units, SYSMAC LINK Units, SYSMAC BUS/2 Masters,  
BASIC Units, Personal Computer Unit, C500 I/O Units,  
C500 Special I/O Units, SYSMAC BUS Masters)  
24  