Monitoring Relays
3-Phase Sequence and Phase Loss
Type DPA53
Product Description
3-Phase monitoring relay for detection of incorrect phase
sequence and phase loss. Using the front knob it can be decided
the undervoltage setpoint of the unit.
Supply range from 208 to 240VAC or 380 to 480VAC covered by
two multivoltage relays. For mounting on DIN-rail.
Housing 17.5mm wide suitable both for back and front panel
mounting.
Property
•
•
•
•
•
•
•
•
•
Knob-adjustable undevoltage detection
Measures its own power supply
Power supply range: 208 to 240 and 380 to 480 VAC (±15%)
Output: 5 A SPDT relay normally energized
For mounting on DIN-rail in accordance with DIN/EN 50 022
17.5 mm DIN-rail housing (DIN 43880)
LED indication for relay and power supply ON
3-phase monitoring relay for phase sequence and phase loss
Detects all phases are present and have the correct sequence
Type Selection
Mounting
DIN-rail
Output
SPDT
Supply: 208 to 240 VAC
DPA 53 C M23
Supply: 380 to 480 VAC
DPA 53 C M48
Input Specifications
Input
L1, L2, L3
Measuring range
M23
M48
M23
M48
160 to 240 VAC
320 to 480 VAC
3% on full scale
4% on full scale
Terminals L1, L2, L3
Measures its own supply
General Specifications
Reaction time
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Repeatability
Indication for
Power supply ON
Relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
@ Max. voltage, 50 Hz
@ Max. voltage, 60 Hz
Storage temperature
Housing
Dimensions
Material
Weight
Screw terminals
Tightening torque
Product standard
Approvals
CE Marking
EMC
Immunity
Emissions
< 100 ms
< 300 ms
(15 min warm-up time)
± 1000 ppm/°C
± 0.5% on full scale
LED, green
LED, yellow
IP 20
2
-20 to +60°C, R.H. < 95%
-20 to +50°C, R.H. < 95%
-30 to +80°C, R.H. < 95%
17.5 x 81 x 67.2 mm
PA66 or Noryl
Approx. 75 g
Max. 0.5 Nm
acc. to IEC 60947
EN 60947-5-1
UL, CSA
CCC (GB14048.5)
L.V. Directive 2006/95/EC
EMC Directive 2004/108/EC
According to EN 61000-6-2
According to EN 61000-6-3
Hysteresis
Output Specifications
Output
Rated insulation voltage
Contact ratings
(AgSnO
2
)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
SPDT relay, N.E.
250 VAC
μ
5 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥
30 x 10
6
operations
≥
10
5
operations
(at 5 A, 250 V, cos
ϕ
= 1)
≤
7200 operations/h
Operating frequency
Dielectric strength
≥
2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 μs)
Supply Specifications
Power supply
Rated operational voltage
through terminals:
M23
M48
Rated operational power
M23
M48
Overvoltage cat. III
(IEC 60664, IEC 60038)
L1, L2, L3
208 to 240 VAC ± 15%,
45 to 65 Hz
380 to 480 VAC ± 15%,
45 to 65 Hz
7 VA @ 230 VAC, 50 Hz
13 VA @ 400 VAC, 50 Hz
Supplied by L1 and L3